Rev.23
35/311
If the unit operates as a definite time, the starting up of the function occurs with 100% of adjusted tap,
and it resets with the 95%.
If the unit operates with curve, the starting up of the function occurs with the 110% of the adjusted tap
and it resets with the 100%. Reset is instantaneous in both cases.
Action time accuracy is ±5% or ±30ms highest of both, over theorical time of action.
Used curves are IEC 60255-151 and IEEE, which are described on corresponding section of this
manual.
4.6.
Function 49. Thermal image protection
Thermal image is a measure of heating and cooling of an electric machine. Unlike overcurrent protection,
do not start counting the time when it detects a fault, but is continuously determining the thermal state
of the machine that monitors. The trip time depends on the thermal constants adjusted, the current
flowing and the prior thermal state of the machine.
The thermal image is calculated based on the following equation:
θ = 100 x (I/I
t
)
2
x (1
– e
-
t/ζ
) + θ’
0
x e
-
t/ζ
where :
•
I, máximum r.m.s. current of three phases
•
I
t,
adjusted tap current
•
ζ, termal constant
•
θ’
0
, initial termal state
The trip time is given by the equation:
t =
ζ x ln { [(I/I
t
)
2
–
(θ’
0
/ 100)
] / [(I/I
t
)
2
- 1] }
The algorithm uses the maximum of the three phase currents. If the maximum is greater than 15% of
the adjusted tap, heating thermal constant is applied. If the maximum is less than 15% of the adjusted
tap cooling thermal constant is taken into account.
The overload function trips when the thermal image reaches the value of 100%. This value is reached
in time when the current flowing is equal to the function adjusted in thermal function.
It provides an adjustable level of thermal imaging to generate an alarm. If the trip occurs, the function of
overload is reset when the thermal image falls below the set alarm level.
As the current measurement algorithm used is r.m.s., in the thermal model is taken into account the
heat produced by the harmonics.
This protection function is adjusted by setting five different parameters
:
Содержание SIL B
Страница 1: ...EN_FANOXTD_MANU_SIL_Feeder_SILB_R023 Docx USER S MANUAL SIL B Feeder Relay...
Страница 8: ...www fanox com Rev 23 8 311 2 DIMENSIONS AND CONNECTION DIAGRAMS 2 1 Equipment front view...
Страница 9: ...www fanox com Rev 23 9 311 2 2 Equipment dimensions...
Страница 10: ...www fanox com Rev 23 10 311...
Страница 11: ...www fanox com Rev 23 11 311 2 3 Cut out pattern CUT OUT PATTERN...
Страница 12: ...www fanox com Rev 23 12 311 2 4 Connection diagrams Analog connections...
Страница 13: ...www fanox com Rev 23 13 311...
Страница 14: ...www fanox com Rev 23 14 311 Digital connections Outputs and Trip circuit supervision...
Страница 15: ...www fanox com Rev 23 15 311 2 5 Terminals IEC 61850 or DNP3 0 protocols...
Страница 17: ...www fanox com Rev 23 17 311 IEC 60870 5 103 protocol...
Страница 25: ...www fanox com Rev 23 25 311 3 3 Functional diagram...
Страница 28: ...www fanox com Rev 23 28 311 3 5 1 SIL B 1 CHARGE CURVE 3 5 2 SIL B 5 CHARGE CURVE...
Страница 38: ...www fanox com Rev 23 38 311 4 6 4 Thermal protection curves This is the thermal curve for 3 minutes...
Страница 91: ...www fanox com Rev 23 91 311...
Страница 140: ...www fanox com Rev 23 140 311...
Страница 194: ...www fanox com Rev 23 194 311 Polarization V 35 0 V C Operating Angle 180 C Halfcone Angle 3 C...
Страница 307: ...www fanox com Rev 23 307 311 50BF init Fault init 79 Closure permission 52 closure permission...
Страница 308: ...www fanox com Rev 23 308 311 12 8 LED s configuration LEDs Blinking Latch Negate d LED On LED 1 LED 2 LED 3 LED 4 LED 5...
Страница 310: ...www fanox com Rev 23 310 311 NOTES...
Страница 311: ...www fanox com Rev 23 311 311...