Menu 3.1.1.1.x - Room temperature regulation, absolute
Air setpoint >
Air setpoint,cool
Temp. setpoint >
Abs. / Rel. >
Cool rel. start >
Cool abs. start >
Heat rel. start >
Heat abs. start >
3.1.1.1.x xxxxxxx
60
80
21,0
Absolute
---
26,0
---
21,0
%
°c
°c
°c
Note
Temp. Setpoint can never be set closer to Heating abs. start or Cooling abs. start
than 0.5 K.
Heating abs. start and Cooling abs. start can never be set closer to each other
than 1 K.
If
the following will be adjusted....
Maximum room temp. is set to a val-
ue lower than Cooling abs. start
Cooling abs. start will automatically reduce
to the same value as Maximum room
temp.
Cooling abs. start is set to a value
lower than (Temp. se 0.5 K)
Temp. setpoint will automatically reduce to
(Cooling abs. start - 0.5 K).
Minimum room temp. is set to a val-
ue higher than Heating abs. start
Heating abs. start will automatically rise to
the same value as Minimum room temp.
Heating abs. start is set to a value
higher than (Temp. setpoint - 0.5 K)
Temp. setpoint will automatically rise to
(Heating abs. start + 0.5 K).
3005167-2022-02-02
Starting up the unit for operation
31/108