Cooling Alarm
Unit
Fault code
Category
Alarm description
Troubleshooting
(See appendix 1: "Simplified diagrams" for the location of dampers, sen-
sors, air directions, etc.)
xx yy
z
43 01
3
Temperature sensor af-
ter the CCW surface in
the supply air duct is
short-circuited.
● Check the sensor's resistance complies with the actual tem-
perature. See temperature resistance table appendix 2.
● If the sensor resistance has significantly changed in value, it
should be replaced.
43 02
3
Temperature sensor af-
ter the CCW surface in
the supply air duct is
open-circuit.
● Check the sensor's resistance complies with the actual tem-
perature. See temperature resistance table appendix 2.
● If the sensor resistance has significantly changed in value, it
should be replaced.
43 03
3
The temperature sen-
sor in the supply to the
CCW surface in the ex-
tract air duct is short-
circuited.
● Check the sensor's resistance complies with the actual tem-
perature. See temperature resistance table appendix 2.
● If the sensor resistance has significantly changed in value, it
should be replaced.
43 04
3
The temperature sen-
sor in the supply to the
CCW surface in the ex-
tract air duct is open-
circuit.
● Check the sensor's resistance complies with the actual tem-
perature. See temperature resistance table appendix 2.
● If the sensor resistance has significantly changed in value, it
should be replaced.
43 05
3
Pressure gas tempera-
ture sensor has short-
circuited.
● Check the sensor's resistance complies with the actual tem-
perature. See temperature resistance table appendix 2.
● If the sensor resistance has significantly changed in value, it
should be replaced.
43 06
3
Pressure gas tempera-
ture sensor has been
interrupted.
● Check the sensor's resistance complies with the actual tem-
perature. See temperature resistance table appendix 2.
● If the sensor resistance has significantly changed in value, it
should be replaced.
43 07
3
Suction gas pressure
sensor has short-
circuited.
● Check connection between sensor and cooling control,
● Contact EXHAUSTO service.
43 08
3
Suction gas pressure
sensor has been inter-
rupted.
● Check connection between sensor and cooling control,
● Contact EXHAUSTO service.
43 09
3
Pressure gas pressure
sensor has short-
circuited.
● Check connection between sensor and cooling control,
● Contact EXHAUSTO service.
43 10
3
Pressure gas pressure
sensor has been inter-
rupted.
● Check connection between sensor and cooling control,
● Contact EXHAUSTO service.
43 11
3
Low pressure guard
has triggered a stop.
Call a cooling technician.
43 12
3
High pressure guard
has triggered a stop.
Call a cooling technician.
Three operational stops due to high pressure are permitted before
this alarm is triggered.