Method
Meth-
od
no.
(1-8)
Description
The following parameters
are set
Menu
Manual con-
trol
1
Constant speed
Manual control of fan speed
● Balance
3.1.1 Operating settings
IAQ. levels >
Air reg. >
Temp. reg. >
Balance >
Regulators >
Supply air
1
1,0
Airflow con-
trol
2
Constant airflow
Maintains the airflow, com-
pensating for changes in the
ducting system, filter soiling,
etc.
● Extract airflow values
for maximum and min-
imum ventilation (see
capacity diagram in
the VEX/CX instruc-
tions)
● Supply air balance rel-
ative to extract air
3.1.1.4 Constant airflow
Setp. maks. >
Setp. min. >
Balance > 1,00
10000l/s
0l/s
Constant
pressure reg-
ulation of ex-
tract air
3
Constant pressure-regulated
extract air with fixed supply
air setting
Requirements:
● MPT-DUCT negative
pressure sensor in the
extract air duct. Available
as an accessory
● Extract airflow values
for maximum and min-
imum ventilation
● Fixed setting for sup-
ply airflow
3.1.1.4 Constant pressure
Extract air:
Setp. max. >
Setp. min. >
Setp. >
Supply air:
1000Pa
0Pa
0l/s
5
Constant pressure-regulated
extract air with slave-control-
led supply air
Requirements:
● MPT-DUCT negative
pressure sensor in the
extract air duct. Available
as an accessory
● Extract airflow values
for maximum and min-
imum ventilation
● Supply air balance rel-
ative to extract air
3.1.1.4 Constant pressure
Extract air:
Setp. max. >
Setp. min. >
Balance >
Supply air:
1000Pa
0Pa
1.00
3005167-2022-02-02
Starting up the unit for operation
23/108