Frequency converter 2
Unit
Fault code
Category
Alarm description
Troubleshooting
(See appendix 1: "Simplified diagrams" for the positioning of dampers,
sensors, air directions, etc.)
xx yy
z
02 01
4
One or more phases
between frequency
converter and motor
is/are short-circuited to
earth
● Check the cable between frequency converter 2 and motor
02 02
4
Max. motor current
from frequency con-
verter exceeds limit by
300%
● Check for low voltage to frequency converter 2
02 03
4
Frequency converter
DC circuit max. voltage
exceeds limit
● Check for overvoltage to frequency converter 2
02 04
2
Frequency converter
DC circuit voltage too
low when motor(s)
start(s)
● Check for low voltage to frequency converter 2
02 05
4
Frequency converter
DC circuit voltage too
low when VEX unit
stops
● Check for low voltage to frequency converter 2
02 06
4
Frequency converter
power supply has lost
a phase
● Check wiring from the power supply connection to the isolation
switch in the VEX unit
● Check cable connections from the isolation switch to frequen-
cy converter 2
02 07
4
Frequency converter
power supply to mo-
tor(s) has lost a phase
● Check the cable between frequency converter 2 and motor
● Check for a short circuit in the motor windings
02 08
4
Frequency converter
overheated (based on
internal calculations)
● Check if the temperature at frequency converter 2 exceeded
the permitted 35°C when the alarm was tripped. If the temper-
ature has been too high, the unit will restart when the air tem-
perature falls below 35°C.
02 10
4
Frequency converter
cooling coil overheated
● Check if the temperature at frequency converter 2 exceeded
the permitted 35°C when the alarm was tripped. If the temper-
ature has been too high, the unit will restart when the air tem-
perature falls below 35°C.
02 11
4
Frequency converter
motor(s) drawing too
much current
Fault on frequency converter 2.
02 12
4
Frequency converter
motor 1 overheated
● Check the motor impeller can turn freely
● Check that the fan impeller is not blocked
02 13
4
Frequency converter
motor 2 overheated
● Check the motor impeller can turn freely
● Check that the fan impeller is not blocked
02 14
4
No modbus communi-
cation to frequency
converter
● Check the cable between the connection board and frequency
converter 2.
3005167-2022-02-02
Alarms
66/108