Fire thermostats
Unit
Fault code
Category
Alarm description
Troubleshooting
(See appendix 1: "Simplified diagrams" for the location of dampers, sen-
sors, air directions, etc.)
xx yy
z
12 01
5
BT40/50, FIRE:
Triggered fire alarm
has stopped VEX/CX
unit
BT40/50, FIRE: In event of Fire: Follow the building emergency
procedure
Fire thermostat triggered when there is no fire:
● The closed circuit is broken. Find out why the fire detection
unit has broken the circuit.
● If no unit is connected – check jumper.
12 02
5
BT70, AUX IN:
Triggered fire alarm
has stopped VEX/CX
unit
BT70, AUX IN:
In event of Fire: Follow the building emergency procedure
Fire thermostat triggered when there is no fire:
● The closed circuit is broken. Find out why the fire detection
unit has broken the circuit.
● If no unit is connected – check jumper.
12 03
3
Fire brigade override
error
The fire brigade override panel has been left in an illegal setting.
Filters
Unit
Fault code
Category
Alarm description
Troubleshooting
(See appendix 1: "Simplified diagrams" for the positioning of dampers,
sensors, air directions, etc.)
xx yy
z
13 01
2
Replace extract air fil-
ter soon
Replace extract air filter soon
13 02
3
Replace extract air fil-
ter!
Replace extract air filter!
13 03
2
Replace outdoor air fil-
ter soon
Replace outdoor air filter soon
13 04
3
Replace outdoor air fil-
ter soon
Replace outdoor air filter soon