Line in menu 3.4
Factory-set and
should not be
changed.
Remarks:
PIR
Activating PIR sensor. Op-
tions:
● Both (Both MIOPIR and
PIRB connected)
● PIR2 (PIRB connected)
● PIR1 (MIOPIR connected)
● None
When the sensor(s) is/are acti-
vated by movement in the
room, the VEX will be overrid-
den and set to comfort level.
Comfort level will be main-
tained for the time set on the
rear of the sensor (PIRB), af-
ter which the VEX will return to
the previous indoor climate
level.
Note: The time interval for
MIOPIR is fixed at 10 minutes
and cannot be changed).
TS
Activation of external tempera-
ture sensor and selection of
type. Options:
● TS DUCT
● TS ROOM
● None
CO2
Activation of CO
2
sensor Op-
tions:
● BMS
● CO2B (sensor connected
to AI SPARE)
● MIOCO2
● None
RH
Activation of RH sensor. Op-
tions:
● BMS
● RHB (sensor connected
to AI SPARE)
● MIORH
● None
Dining solution
ALC
x
ALC menu: This is where ALC
is activated and deactivated.
Other settings should not be
changed.
Menu 3.4 Connecting heating and cooling units
Location
A heating coil and a cooling unit can be connected to the VEX. The example be-
low (VEX200) shows the position of the coils in relation to the VEX unit.
3005167-2022-02-02
Starting up the unit for operation
19/108