Program example
5.2.2.1 Weekday
1 IAQ. level >
1 Time of day >
2 IAQ. level >
2 Time of day >
3 IAQ. level >
3 Time of day >
4 IAQ. level >
4 Time of day >
5 IAQ. level >
5 Time of day
Standby
06:00
Comfort
07:30
Economy
17:30
OFF
00:00
Inactive
--:--
Time interval
Indoor air quality level
06:00 - 07:30
Standby
07:30 - 17:30
Comfort
17:30 - 00:00
Economy
00:00 - 06:00
OFF
Menu 7 - Safety functions
Menu 7.1 - Fire alarm
Four operating
modes
There are four different operating modes in the event of a fire. The selected oper-
ating mode must meet regulatory standards.
Go to menu
7.1 and select
mode
Operating mode
Fans
LSF
LSA
LS ALC*
1 (factory set-
ting)
Supply air and
extract air
stopped
Closed
Closed
Closed
2
Supply air
100% and ex-
tract air stop-
ped
Opened
Closed
Closed
3
Supply air
stopped and
extract air
100%
Closed
Opened
Opened
4
Supply and
extract air
100%
Opened
Opened
Opened
*LS ALC is extract air damper for Automatic leakage control
Activation of oper-
ating mode
The selected operating mode under the function "Fire alarm" is activated if the
closed circuit in any of the two inputs Fire and AUX IN on EXact2 main board are
broken.
3005167-2022-02-02
Starting up the unit for operation
48/108