Example
Supply air temperature is
Airflow...
A
Lower than Minimum
Equivalent to Minimum (or lowest)
airflow
B
Between Minimum and Start
increases gradually between mini-
mum airflow and the set airflow
C
Greater than Start
Equivalent to set airflow
NB
● When this function is active, a large imbalance can occur in the airflows, as
only the supply airflow is reduced while the extract airflow is maintained at the
required level
● CO
2
and RH sensors are overridden by this function.
Menu 3.1.2.4 - Outdoor compensation of airflow
Function
When the control system is operating, this function reduces the required airflow in
the event of falling outdoor air temperature.
Selecting outdoor
compensation
Activate in Menu 3.1.2.4.
Example
3005167-2022-02-02
Starting up the unit for operation
39/108