HC Controller
Device
Fault code
Category
Alarm description
Troubleshooting
(See appendix 1: "Simplified diagrams" for the positioning of dampers,
sensors, air directions, etc.)
xx yy
z
16 01
1
MHCW: Module config-
ured incorrectly. Check
CN6 on circuit board.
Check the jumper in the CN6 connector on the heat control circuit
board
MHCW
: - there must be a jumper across 7 and 8.
MHCE
: - a jumper must not be fitted.
16 02
1
HCW: Fan speed tem-
porarily reduced
HCW
: Fan speed temporarily reduced because warning limit for
frost protection of water heating coil has been reached
16 03
1
HCW: VEX/CX stop
temporarily
HCW
: Fan speed temporarily reduced because stop temperature
for frost protection of water heating coil has been reached.
16 04
1
HCW: VEX/CX stop.
HCW
: Fan speed stopped because of frost alarm on the water
heating coil.
16 05
1
HCE: Run-on operating
because electric heat-
ing coil warm in last
three minutes.
HCE
: The fans run on for three minutes after the electric heating
coil has been in operation.
16 06
1
HC: Heat control cur-
rently run locally due to
service
HC
: Heat control temporarily controlled by Lodam Multi Tool. Over-
ride lasts for max. 60 minutes
16 07
1
HC: Heat control safety
functions overridden lo-
cally due to service
HC
: Heat control temporarily controlled by Lodam Multi Tool. Over-
ride lasts for max. 60 minutes.
16 10
1
HCE: Heat output re-
duced due to low air-
flow in supply air duct
HCE
: When the airflow is between 0.5 and 1.5 m/s over the electric
heating elements, full heat output is not permitted. Full heat output
is permitted only when airflow is more than 1.5 m/s over the heat-
ing elements.
16 13
4
HC: Heat control de-
tected which was not
selected in VEX/CX
configuration
HC
: The heating coil is configured in menu 3.4 "Accessories".
16 14
4
MHC: Heat control
configured incorrectly
in connection with se-
lected VEX/CX config-
uration
Check the jumper in the CN6 connector on the heat control circuit
board
MHCW
: - there must be a jumper across 7 and 8.
MHCE
: - a jumper must not be fitted.
16 15
4
MHCW: No modbus
communication to wa-
ter heat control
MHCW
:
● Check the modbus cable between the connection board (EX-
act)/main board (EXact2) and MHCW.
● Check modbus cable for faults from HCW to the other units.
16 16
3
MHCE: No modbus
communication to elec-
trical heating control
MHCE
:
● Check the modbus cable between the connection board (EX-
act)/main board (EXact2) and MHCE.
● Check modbus cable for faults from HCE to the other units
3005167-2022-02-02
Alarms