Menu 3.1.2.2 - Humidity compensation of airflow
Requirements
A humidity sensor (RHB, MIO-RH, BMS) must be fitted in order to be able to se-
lect humidity compensation of the airflow. The sensor must be installed in the
room in which you wish to make compensation, such as a bathroom. Connection
of the sensor is described in the additional instructions accompanying the sensor.
Function
When the control system is operating, this function increases airflow in the event
of increasing humidity levels.
NB
● Cannot be activated if air regulation method 8 is selected.
Selecting humidity
compensation
Activate in Menu 3.1.2.2.
Example
Air humidity level is
Airflow...
A
less than Start
is the same as set value
B
between Start and Maximum
increases gradually to a high value,
depending on the current air humidity
(RH level)
C
greater than Maximum
is increased to maximum air replace-
ment
Menu 3.1.2.3 - Airflow reduction
Function
When the control system is operating, this function reduces the required supply air
airflow in the event of falling supply air temperature. This makes it possible to
maintain the required supply air temperature longer.
Selecting airflow re-
duction
Activate in Menu 3.1.2.3.
3005167-2022-02-02
Starting up the unit for operation
38/108