7 Acceptance/Protection Function Test Guide
D02706R02.30
L-PRO 4000 User Manual
7-9
The multiplier used to compensate phase-to-ground impedances:
21N Reach Settings
Zone 1 Reach: Mho 4.72
Zone 2 Reach: Quadrilateral X: 7.38
, R: 6.00
Zone 3 Reach: Mho Forward 17.7
, Reverse 0.50
Zone 4 Reach: Mho Forward 0.00
, Reverse 4.72
Compensated 21N1 setting 4.72
(Zone 1 phase-to-ground compensated Mho
impedance):
where
Z
1
- Positive Sequence Impedance
Z
2
- Negative Sequence Impedance
K
0
- Factor
(6)
1 +
K
0
= (1 + 0.57
-9.5
)
= (1 + 0.562 –
j
0.094)
= (1.562 –
j
0.094) = 1.569
3.5
(7)
(8)
K
0
Z
0
Z
1
–
3
Z
1
------------------
=
3.38
j
9.57
+
17.7 80
------------------------------
10.15 70.52
17.7 80
----------------------------------
0.57
9.5
–
=
=
=
4.41 1.03
–
j
15.38
j
5.81
–
+
3 5.9 80
------------------------------------------------------------------------------------
=
4.72
80
1.569
3.5
–
7.40
76.5
=