Appendix B IED Settings and Ranges
Appendix B-10
L-PRO 4000 User Manual
D02706R02.30
27 Aux
Disabled
Default pickup value
25.0 V
Pickup delay
5,00 s
60
Disabled
I1 Blocking
7.5 A
3I0 Blocking
1.0 A
60 CTS Main
Disabled
60 CTS Aux
Disabled
81-1
Disabled
Default pick
57.600 Hz
Fixed level/Rate of change
81-2
Disabled
Default pick
57.000 Hz
Fixed level/Rate of change
81-3
Disabled
Default pick
61.800 Hz
Fixed level/Rate of change
81-4
Disabled
Default pick
62.400 Hz
Fixed level/Rate of change
50LS Main (Input 1)
Disabled
Pickup value
50.0 A
Pickup delay
1.00 s
50LS Aux (Input 2)
Disabled
Pickup value
50.0 A
Pickup delay
1.00 s
50LS Input 3
Disabled
Pickup value
50.0 A
Pickup delay
1.00 s
50LS Input 4
Disabled
Pickup value
50.0 A
Pickup delay
1.00 s
50BF Main
Disabled
Main pickup delay 1
0.200 s
Main pickup delay 2
0.200 s
Main Breaker current pickup
1.00 A
50BF Aux
Disabled
Main pickup delay 1
0.200 s
Main pickup delay 2
0.200 s
Main Breaker current pickup
1.00 A
50
Disabled
51
Disabled
50N
Disabled
51N
Disabled
Содержание L-PRO 4000
Страница 1: ...L PRO 4000 Transmission Line Protection Relay User Manual Version 2 3 Rev 0...
Страница 2: ......
Страница 4: ......
Страница 8: ......
Страница 10: ......
Страница 14: ......
Страница 40: ......
Страница 50: ......
Страница 116: ......
Страница 146: ......
Страница 218: ......
Страница 252: ...Appendix B IED Settings and Ranges Appendix B 34 L PRO 4000 User Manual D02706R02 30...
Страница 260: ......
Страница 270: ......
Страница 302: ......
Страница 308: ......
Страница 310: ......
Страница 311: ...D02706R02 30 L PRO 4000 User Manual Appendix K 1 Appendix K Function Logic Diagram Diagram in plastic sleeve...
Страница 312: ......