7 Acceptance/Protection Function Test Guide
D02706R02.30
L-PRO 4000 User Manual
7-25
3. Apply the following 3-phase currents to the relay main ac current terminals:
Ph A: 300 – 301, 5.3 A <-30
Ph B: 302 – 303, 5.3 A <210
Ph C: 304 – 305, 5.3 A <90
4. Observe target Load Encroachment.
5. Disable Load Encroachment, repeat steps 2-3.
6. Observe 21P3 Alarm/Trip.
End of Load Encroachment test.
Weak Infeed
Test
Weak Infeed tripping operates on 4 basic conditions:
1. Low Positive Sequence Voltage (27V1) or High Neutral Voltage (59V0)
2. No Zone 2 or Zone 4 reverse element picked up.
3. Loss of Potential (60) element dropped out
4. Permissive trip received from the remote end
Figure 7.16: Weak Infeed Logic
For this test apply 0 voltage and 0 current to the relay with no prefault. This
causes the first 3 conditions to be met: (27V1, NOT (Zone 2 OR Zone 4R),
NOT Loss of Potential).
In this case a Virtual Input is set up to simulate the Permissive Trip Receive
contact via ProLogic.
Figure 7.17: Scheme Selector Settings (Offliner)
113
111
0
TWD3
3ms
TWD2
108
110
6ms
TWD1
112
20ms
0
60
27 V1
59 V0
Weak
Infeed
Enable
Switch
21-2
21-4R
Receiver
Scheme
Trip
Scheme
Send
Содержание L-PRO 4000
Страница 1: ...L PRO 4000 Transmission Line Protection Relay User Manual Version 2 3 Rev 0...
Страница 2: ......
Страница 4: ......
Страница 8: ......
Страница 10: ......
Страница 14: ......
Страница 40: ......
Страница 50: ......
Страница 116: ......
Страница 146: ......
Страница 218: ......
Страница 252: ...Appendix B IED Settings and Ranges Appendix B 34 L PRO 4000 User Manual D02706R02 30...
Страница 260: ......
Страница 270: ......
Страница 302: ......
Страница 308: ......
Страница 310: ......
Страница 311: ...D02706R02 30 L PRO 4000 User Manual Appendix K 1 Appendix K Function Logic Diagram Diagram in plastic sleeve...
Страница 312: ......