7 Acceptance/Protection Function Test Guide
7-2
L-PRO 4000 User Manual
D02706R02.30
Calibration
The relay is calibrated before it leaves the factory; but if component changes
are made within the relay, the user may need to do a re-calibration.
To perform a calibration, the user must be logged into the relay using Relay
Control Panel at the Service access level to the front USB Port. Proceed to the
Utilities>Analog Input Calibrate
. The
Calibrate
menu leads the user through
every analog input and prompts the user to apply the appropriate quantity.
Figure 7.1: Enter actual applied signal level
Set nominal CT secondary current to either 5 A or 1 A, and nominal
system frequency to either 60 Hz or 50 Hz. This example uses 5 A/
60 Hz.
Before beginning a new calibration, establish the accuracy of the
equipment being used.
Содержание L-PRO 4000
Страница 1: ...L PRO 4000 Transmission Line Protection Relay User Manual Version 2 3 Rev 0...
Страница 2: ......
Страница 4: ......
Страница 8: ......
Страница 10: ......
Страница 14: ......
Страница 40: ......
Страница 50: ......
Страница 116: ......
Страница 146: ......
Страница 218: ......
Страница 252: ...Appendix B IED Settings and Ranges Appendix B 34 L PRO 4000 User Manual D02706R02 30...
Страница 260: ......
Страница 270: ......
Страница 302: ......
Страница 308: ......
Страница 310: ......
Страница 311: ...D02706R02 30 L PRO 4000 User Manual Appendix K 1 Appendix K Function Logic Diagram Diagram in plastic sleeve...
Страница 312: ......