6 Offliner Settings Software
D02706R02.30
L-PRO 4000 User Manual
6-21
Line Parameters
Figure 6.18: Line Parameters
Table 6.11: Line Parameters
Line
Line to Line voltage
1.00 to 2000.00 kV primary
Line Length (km/mile)
0.50 to 2000.00
Sequence Impedance
Positive Sequence Impedance (Z1) (ohm sec-
ondary)
0.01 to 66.00 (5A)
0.05 to 330.00 (1A)
Positive Sequence Angle (Z1) (deg)
5.0 to 89.0
Zero Sequence Impedance (Z0) (ohm)
0.01 to 300.00 (5A)
0.05 to 1500.00 (1A)
Zero Sequence Angle (Z0) (deg)
5.0 to 89.0
K0
K0 Override
Enable/Disable
K0 Magnitude
0.00 to 10.00
K0 Angle (deg)
-180.0 to 180.0
Mutual Compensation