7 Acceptance/Protection Function Test Guide
7-44
L-PRO 4000 User Manual
D02706R02.30
3. Apply 3-phase negative sequence currents to the relay terminals:
Ph A: 300
–
301, 5.1A
-80
Ph B: 302
–
303, 5.1A
+40
Ph C: 303
–
304, 5.1A
+160
Observe 46-50 Trip = High
4. Slowly ramp up Phase A current to activate Directional Control:
At 5.67 to 5.73 A (expect 5.7 A):
46-50 Trip = Low
5. Turn currents off.
End of Directional 50ILpos Threshold test.
50BF (Breaker
Fail) and 50LS
(Low Set
Overcurrent)
Tests
Settings
Main:
• 50LS Pickup: 1.0 A,
• Time Delay: 0.00 seconds
• 50BF Time Delay 1: 5.0 seconds
• 50BF Time Delay 2: 10.0 seconds
Auxiliary:
• 50LS Pickup: 1.0 A
• Time Delay: 0.00 seconds
• 50BF Time Delay 1: 5.0 seconds
• 50BF Time Delay 2: 10.0 seconds
Input 3:
• 50LS Pickup: 0.3 A
• Time Delay: 1.00 second
(50LS used with Virtual Input 3 to make Breaker Fail for Breaker 3)
Input 4:
• 50LS Pickup: 0.3 A
• Time Delay: 1.00 second
(50LS used with Virtual Input 4 to make Breaker Fail for Breaker 4)
Main and Aux. Breaker Fails are set to be initiated via the Output Matrix from
50LS Pickup (1.0 A Main and Aux and 0 time delay). Note: Requires a mini-
mum of 0.2 A on any phase to arm Breaker Fail.
Содержание L-PRO 4000
Страница 1: ...L PRO 4000 Transmission Line Protection Relay User Manual Version 2 3 Rev 0...
Страница 2: ......
Страница 4: ......
Страница 8: ......
Страница 10: ......
Страница 14: ......
Страница 40: ......
Страница 50: ......
Страница 116: ......
Страница 146: ......
Страница 218: ......
Страница 252: ...Appendix B IED Settings and Ranges Appendix B 34 L PRO 4000 User Manual D02706R02 30...
Страница 260: ......
Страница 270: ......
Страница 302: ......
Страница 308: ......
Страница 310: ......
Страница 311: ...D02706R02 30 L PRO 4000 User Manual Appendix K 1 Appendix K Function Logic Diagram Diagram in plastic sleeve...
Страница 312: ......