7 Acceptance/Protection Function Test Guide
7-22
L-PRO 4000 User Manual
D02706R02.30
End of 21P2 test.
21N2 Ground
Distance Test
Zone 2 Phase-to-Neutral Under Impedance
Settings
• Positive Sequence Secondary Line Impedance (100% of line) = 5.9
• Positive Sequence Line Angle (Z1) = 80
• 21N2 = 7.38
(Maximum Reach = 125% of line at maximum torque angle
of 80
) compensated as per 21N calculations to: 11.58
76.5
• Resistive Component compensated to: 9.41
-3.5
• Time Delay = 0 (expect 1.3 cycles, 22 ms or less)
• 3I0 Current Supervision = 1.5 A (minimum zero sequence current to allow
21N2 to operate)
• I Phase Current Supervision = 1.5 A (minimum phase current to allow 21N2
to operate)
Figure 7.14: Ground Distance Logic (21N)
This test demonstrates testing a single line (Phase A) to a ground fault.
Preliminary calculations
Since this is a single-phase test, use the compensated impedance value calcu-
lated above; the calculated fault impedance
Z
fault
is:
0
4ms
21N# - Zan
50 Ia
Directional Element
21N# - Zbn
50 Ib
Directional Element
21N# - Zcn
50 Ic
Directional Element
N - Zone #
60
TN#
0
Out 1
21N
Generic Phase Distance
Logic (# = any zone)
50N 3IO
50N 3IO
50N 3IO
142
141
138
139
140
(29)
Z
fault
V
fault
I
fault
---------------
=
Содержание L-PRO 4000
Страница 1: ...L PRO 4000 Transmission Line Protection Relay User Manual Version 2 3 Rev 0...
Страница 2: ......
Страница 4: ......
Страница 8: ......
Страница 10: ......
Страница 14: ......
Страница 40: ......
Страница 50: ......
Страница 116: ......
Страница 146: ......
Страница 218: ......
Страница 252: ...Appendix B IED Settings and Ranges Appendix B 34 L PRO 4000 User Manual D02706R02 30...
Страница 260: ......
Страница 270: ......
Страница 302: ......
Страница 308: ......
Страница 310: ......
Страница 311: ...D02706R02 30 L PRO 4000 User Manual Appendix K 1 Appendix K Function Logic Diagram Diagram in plastic sleeve...
Страница 312: ......