INSTALLATION INSTRUCTION
Faktaansvarig - Subject responsible
3
HARDWARE
INSTALLATION
3.1
ASB 150 01
If the sensor is to be placed outside it is preferably
mounted on a wall outside, with the attached screw,
that is not placed in direct sunlight. A desirable place is
for instance a shady place under the roof. Try not to
place the sensor near a window that is often open for
airing or near an output for the ventilation.
The cable is preferably drawn as little as possible
outdoor.
The cable should be run to ELU-A10 directly,
superfluous cable is to be cut off.
The wires are connected to pin 1 & 2 in the molex
connector (non-polarized connection).
The molex connector is connected to field 4*3 to a
ELU-A10 printed circuit board (please see section
2.1.2 for from what revision it is possible)
If the sensor is located more than 10 m from the
exchange, we recommend you to use a twisted pair
cable for extension.
3.2
ASB 150 02
If the sensor is to be placed outside it is preferably
mounted on a wall outside, with the attached screw,
that is not placed in direct sunlight. A desirable place is
for instance a shady place under the roof. Try not to
place the sensor near a window that is often open for
airing or near an output for the ventilation. The cable is
preferably drawn as little as possible outdoor and
directly to the MDF, superfluous cable is to be cut off.
If the sensor is located more than 10 m from the
exchange, we recommend you to use a twisted pair
cable for extension.
The wires are connected to the connection block pin
a5 and b5, a6 and b6, a7 and b7 (non-polariz)
0 1 2 3 8
Field connection by
means of connector
RNT 247 011/22 (MOLEX)
10 9
8
7
6
5
4
3
2
1
Field 2
Field 4
Field 6
Board
position
To
line board
ELU-A10
Temperature sensor
4*3
MDF
Not
necessary
kit RPM 603 339/1