66
CTC EcoLogic Pro/Family
For the property owner
4.5.4.4 Quick start Compressor
The delay normally prevents compressor start earlier
than 10 min. after compressor stop. The delay is also
activated in the event of a power failure, or the irst time
after production is started. This function speeds up
this process. For EcoLogic systems 1 to 3, the degree
minute loss is set to the value that starts all heat pumps.
4.5.4.5 Software update, USB
This is only for service engineers. This option can be
used to update the software in the display via USB. The
software update process is complete when the start
menu appears.
4.5.4.6 Write log to USB
This is only for service engineers. This function can be
used to save logged values to a USB memory stick.
4.5.4.7 Re-installation
This command re-launches the installation sequence.
See the chapter on “First start”.
4.5.4.8 Calibration Sensor
Primary low VS 1°C (B1)
0.0 (-3.0 to 3.0)
Correction of primary low sensor B1.
Primary low VS 2°C (B2)
0.0 (-3.0 to 3.0)
Correction of primary low sensor B2.
Room temperature 1°C (B11)
0.0 (-3.0 to 3.0)
Correction of room sensor B12.
Room temperature 2°C (B12)
0.0 (-3.0 to 3.0)
Correction of room sensor B12.
Outdoor temperature °C (B15)
0.0 (-3.0 to 3.0)
Correction of outdoor sensor (B15).
Out from solar panels °C (B31)*
0.0 (-3.0 to 3.0)
Correction of temperature sensor on solar panels for
outgoing temperature.
Into solar panels °C (B30)*
0.0 (-3.0 to 3.0)
Correction of temperature sensor on solar panels for
incoming temperature.
!
NOTE! The power to the product
must not be interrupted, under any
circumstances, during the update
process.
!
NOTE! Turn off the power and
always restart the product after the
program update! Several minutes
may pass before the display com-
municates clearly after restart.
Содержание CTC EcoLogic Family series
Страница 2: ......
Страница 3: ...162 105 48 3 2016 04 08 Installation and Maintenance Manual CTC EcoLogic Pro Family...
Страница 67: ...67 CTC EcoLogic Pro Family For the property owner...
Страница 120: ...120 CTC EcoLogic Pro Family For the installer 11 Wiring diagram...
Страница 121: ...121 CTC EcoLogic Pro Family For the installer...
Страница 127: ......
Страница 128: ...Enertech AB P O Box 309 SE 341 26 Ljungby Sweden www ctc se www ctc heating com 162 105 48 3 2016 04 08...