4.5.2.4 DHW tank
This menu indicates whether the DHW tank has been
dei ned in the
Installer/Dei ned system/DHW tank menu.
Sensor B5 measures the temperature in the hot water
tank.
Stop temp. HP °C
55 (20 to 60)
At the selected temperature, the heat pump stops
charging towards the hot water tank.
Start/stop diff °C
5 (3 to 7)
Hysteresis before the heat pump starts or stops the
charging of the hot water tank.
Extra DHW stop temp. °C
60 (20 to 62)
This menu is used to specify the setpoint for the heat
pump to charge hot water.
Max. time DHW
20 (5 to 60)
This specii es the maximum time for which the heat
pump heats the hot water tank.
Max. time heat
40 (5 to 60)
This is the maximum time for which the heat pump
heats the heating circuit, if hot water charging is
required.
Delay heating calc.
3 (1 to 7)
The charge temperature is high after hot water charging.
During the set time period, the primary l ow temperature
is ignored in terms of the degree minute calculation.
Add heat DHW
Demand (Yes/No/Demand)
This menu is used to dei ne whether additional heat
needs to be active in parallel with the heat pump
charging the hot water tank.
Yes means that the setpoint for the additional heat is
automatically set to the same as the setpoint for the
heat pump of the DHW tank.
Demand means that the
additional heat works according to the value that has
been set for DHW tank additional heat.
No means that
additional heat should not be active in the event of DHW
charging.
Add heat DHW relay
No (Yes/No)
If
Yes is selected, additional heat is active during hot
water charging. If
No is selected, the additional heat is
blocked.
Add heat DHW 0–10 V*
3 (No/1 to 10)
If
Yes (0.1–10 V) is selected, additional heat is active
during hot water charging. If
No is selected, the
additional heat is blocked.
Add heat DHW EcoMiniEl Step 3 (No/Step 1 to 3)
If
Yes (steps 1 to 3) is selected, additional heat is
active during hot water charging. If
No is selected, the
additional heat is blocked.
DHW tank
Stop temp. HP °C
55
Start/stop diff. °C
5
Extra DHW stop temp. °C
60
Max. time DHW
20
Max. time heating
40
Delay heating calc
3
Add heat DHW
Demand
Add heat DHW relay
Yes
Add heat DHW 0-10V
3.0
Add heat DHW EcoMiniEl
Step 3
Min. temp. °C
45
Periodic extra DHW, days
14
Max. temp. diff. end DHW °C
3
Start/stop diff. HP2 °C
3
Stop DHW diff. max.
3
Run time DHW circ.
4
Cyclic time DHW circ.
15
Diff. start ext. DHW tank
5
Timer DHW circ.
*Applies to the CTC EcoLogic PRO only.
Содержание CTC EcoLogic Family series
Страница 2: ......
Страница 3: ...162 105 48 3 2016 04 08 Installation and Maintenance Manual CTC EcoLogic Pro Family...
Страница 67: ...67 CTC EcoLogic Pro Family For the property owner...
Страница 120: ...120 CTC EcoLogic Pro Family For the installer 11 Wiring diagram...
Страница 121: ...121 CTC EcoLogic Pro Family For the installer...
Страница 127: ......
Страница 128: ...Enertech AB P O Box 309 SE 341 26 Ljungby Sweden www ctc se www ctc heating com 162 105 48 3 2016 04 08...