39
CTC EcoLogic Pro/Family
For the property owner
4.5.2.2 Heat pump
Compressor
Blocked (Permitted/Blocked)
The heat pump is supplied with a blocked compressor.
Permitted means that the compressor is allowed to
operate.
Stop at outdoor temp °C
-22 (-22 to 10)
This menu is displayed only if the heat pump is an
EcoAir model, and includes settings for the outdoor
temperature at which the compressor is no longer
permitted to operate. The heat pump starts 2°C above
the set value. The lowest outdoor temperature required
for start is -18°C.
Start at degree minute
-60 (-900 to -30)
This states at which degree minute the A1 heat pump
will start. Degree minute calculation is used only for
EcoLogic systems 1, 2 and 3.
Max. prim. l ow HP diff. °C
10 (3 to 20)
If the actual value for the primary l ow is the same as the
setpoint plus the set value and the degree minutes are
less than the start value for the i rst heat pump (factory-
set to -60), the degree minutes are set to the start value
for the i rst heat pump.
If the actual value for the primary l ow is greater than the
setpoint plus the set value and the degree minutes are
less than 0, the minutes are set to 0.
If the actual value for the primary l ow is less than or
equal to the setpoint minus the set value, the degree
minutes are set to the start value for the i rst heat pump
(factory-set to -60).
Max. prim. l ow HP add heat diff. °C
14 (5 to 20)
If the actual value for the primary l ow is less than or
equal to the setpoint minus the set value, the degree
minutes are set to the highest set start value for the
additional heat (factory-set to -500).
Diff. between HP
-60 (-200 to -30)
This dei nes the difference (measured in degree minutes)
at which the heat pumps will be started if necessary.
Applies to EcoLogic systems 1, 2 and 3 only.
Delay between HP
30 (5 to 180)
This is used to set the delay time before the second
heat pump in the system is allowed to start, when the
i rst heat pump is already operating. This value is also
valid for the amount of time that will pass before the
third heat pump is allowed to start, when the i rst and
second heat pumps are operating, and so on.
Applies to EcoLogic systems 4, 5 and 6 only.
Čeština
Eesti
Polski
Slovenščina
Deutsch
Heat pump 1
Compressor Permitted
Stop at outdoor temp. °C
-22
Start at degree minute
-60
Max primary HP diff °C
10
Max primary HP Add diff °C
14
Diff. between HP
-60
Delay between HP
30
Prio. EcoAir/EcoPart °C
7
Cont. brine pump on
No
Compressor stop at brine °C
-5
Brine pump on 10 days
Off
Tariff HP
Off
Smart block HP
No
EP
System
Heat-
pump
EA
EA(M)
1 2 3
1-10
EP
System
Heat-
pump
EA
EA(M)
4 5 6
1
Содержание CTC EcoLogic Family series
Страница 2: ......
Страница 3: ...162 105 48 3 2016 04 08 Installation and Maintenance Manual CTC EcoLogic Pro Family...
Страница 67: ...67 CTC EcoLogic Pro Family For the property owner...
Страница 120: ...120 CTC EcoLogic Pro Family For the installer 11 Wiring diagram...
Страница 121: ...121 CTC EcoLogic Pro Family For the installer...
Страница 127: ......
Страница 128: ...Enertech AB P O Box 309 SE 341 26 Ljungby Sweden www ctc se www ctc heating com 162 105 48 3 2016 04 08...