Notes on Safety
The Silometer FMC 672 Z/677 Z is a level measurement transmitter which can be used
with a variety of probes and sensors. It must be installed by qualified personnel according
to the instructions in this manual.
Certificates
The Silometer FMC 672 Z/677 Z transmitter is available with certificate. The Table below
indicates the combinations available and conditions for installation. Full details can be
taken from the certificates. Please note that where quoted technical data differs from that
listed in Section 2.6, that in the certificate applies.
Certificate
Instruments
Notes
PTB 02 ATEX 2203 X Silometer FMC 672 Z/677 Z
II (1) GD
[EEx ia] IIC/IIB,
install outside Ex-area
PTB 98 ATEX 2215 X DC 12 TE, DC .. TE ., DC .. E ., DC ..
Capacitance probes
11500 Z(M), 11961 (Z), 21561 (Z)
electronic insert EC 16/17/27/37/47 Z,
FEC 12, HTC 16/17/27 Z, HTC 10 E,
HMC 37/47 Z
II 1/2 G, II 2 G,
EEx ia IIC/IIB T6
PTB 98 ATEX 2215 X DC 12 TE, DC .. TE ., DC .. E ., DC ..
Capacitance probes
11500 Z(M), 11961 Z, 21561 Z
electronic insert EC 17/37/47 Z, FEC 12
II 1 G,
EEx ia IIC/IIB T6
Z-65.13-107
DC 12 TE, DC .. TE ., DC .. E ., DC ..
Capacitance probes
11500 Z, 11961 Z, 21561 Z
electronic insert EC 37/47 Z, FEC 12,
HMC 37/47 Z
FMC 470, FMC 671/672 Z,
FMX 570 Z, FMX 770,
SIF 100/110
Continuous level measurement
for overspill protection in
stationary vessels
(for storage of non-combustible,
water-polluting liquids)
German Lloyd
GL No. 97517 HH
Silometer FMC 672 Z
Capacitance probes
electronic insert EC 37 or EC 47
electronic insert EC 17 Z
Level indication on channel 1
(EC 37 Z or EC 47 Z)
Level limit detection on channel 2
(EC 17 Z)
Suitable for unlimited use within
the rules
Safety conventions
In order to highlight safety-relevant or alternate operation procedures in the manual the
following conventions have been used, each indicated by a corresponding icon in the
margin.
Note!
•
A note highlights actions or procedures which, if not performed correctly, may
indirectly affect operation or may lead to an instrument response which is not
planned.
Caution!
•
Caution indicates actions or procedures which, if not performed correctly, may lead
to personal injury or incorrect functioning of the instrument
Warning!
•
A warning indicates actions or procedures which, if not performed correctly, will
lead to personal injury, a safety hazard or destruction of the instrument
Silometer FMC 672 Z/677 Z
Notes on Safety
3