10.4
Differential level measurement
Start
Chapter 8, Section 8.1
- Channel 1 = level,
Channel 2 = difference
- level difference is displayed at V4H0
- level probe 1is displayed at V0H0
Calibration
Chapter 8, Section 8.1
- Order of calibration not critical
- A linearization can be performed at
channel 1
Set analogue output signal (optional)
Chapter 6
- Enter settings in the units selected
during calibration
Set relay parameters(optional)
Chapter 7
- Relay 2 can be assigned to channel 1
by entering 1 at V5H4
Lock parameter matrix (optional)
Chapter 4, Section 4.6
Reset parameters:
V9H5
Enter »fo«
V3H5/V7H5
Enter »S«
V3H6/V7H6
Select mode
V8H0
3 = Differential measurement
»Empty« calibration
V0H1
»Full« calibration
V0H2
Select output range
V0H3
0 = 0
…
20 mA/0
…
10 V,
1 = 4
…
20 mA/2
…
10V
Set output damping
V0H4
Set 0/4 mA value
V0H5
Set 20 mA value
V0H6
Set output at fault
V0H7
0 = -10% (-2 mA/-1 V)
1 = +110% (+22 mA/11V)
2 = last measurement
Set switch point relay 1
V1H0
Set fail-safe mode
V1H1
0 = Minimum
1 = Maximum
Set switching hysteresis V1H2
Set status on alarm
V1H3
0 = de-energises
1 = depends on V0H7
Set parameters in Channel 2
»Empty« calibration
V4H1
»Full« calibration
V4H2
Select output range
V4H3
0 = 0
…
20 mA/0
…
10 V,
1 = 4
…
20 mA/2
…
10V
Set output damping
V4H4
Set 0/4 mA value
V4H5
Set 20 mA value
V4H6
Set output at fault
V4H7
0 = -10% (-2 mA/-1 V)
1 = +110% (+22 mA/11V)
2 = last measurement
Set switch point relay 2
V5H0
Set fail-safe mode
V5H1
0 = Minimum
1 = Maximum
Set switching hysteresis V5H2
Set status on alarm
V5H3
0 = de-energises
1 = depends on V4H7
Lock parameter matrix
V8H9
Silometer FMC 672 Z/677 Z
Chapter 10: Quick Programming Guide
54
Содержание Silometer FMC 672 Z
Страница 6: ...Silometer FMC 672 Z 677 Z Notes on Safety 4...
Страница 59: ...Silometer FMC 672 Z 677 Z Operating matrix...
Страница 62: ...Silometer FMC 672 Z 677 Z Operating matrix...
Страница 63: ...Silometer FMC 672 Z 677 Z Operating matrix...