10.5
Level measurement with reference probe
Start
Chapter 8, Section 8.2
- Channel 1 = level,
Channel 2 = reference probe
- Level is displayed at V0H0,
Correction factor at V4H0
Calibration
Chapter 8, Section 8.2
- After calibration level/volume is
displayed at V0H0
- Minimum level = 3% measuring
probe length
Set analogue output signal (optional)
Chapter 6
- Enter settings in the units selected
during calibration or linearization
Set relay parameters (optional)
Chapter 7
- Assign relay 2 to channel 1 (level
controlled) by entering 1 at V5H4
Lock parameter matrix (optional)
Chapter 4, Section 4.6
Reset parameters:
V9H5
Enter »fo«
V3H5/V7H5
Enter »S«
V3H6/V7H6
Select mode
V8H0
5 = Reference measurement
Reference probe uncovered
Enter 100
V4H2
Enter 0
V4H0
»Empty« calibration
V0H1
Reference probe covered
Enter 100
V4H2
»Full« calibration
V0H2
Minimum level
V8H3
Select output range
V0H3
0 = 0
…
20 mA/0
…
10 V,
1 = 4
…
20 mA/2
…
10V
Set output damping
V0H4
Set 0/4 mA value
V0H5
Set 20 mA value
V0H6
Set output at fault
V0H7
0 = -10% (-2 mA/-1 V)
1 = +110% (+22 mA/11V)
2 = last measurement
Set switch point relay 1
V1H0
Set fail-safe mode
V1H1
0 = Minimum
1 = Maximum
Set switching hysteresis V1H2
Set status on alarm
V1H3
0 = de-energises
1 = depends on V0H7
Select output range
V4H3
0 = 0
…
20 mA/0
…
10 V,
1 = 4
…
20 mA/2
…
10V
Set output damping
V4H4
Set 0/4 mA value
V4H5
Set 20 mA value
V4H6
Set output at fault
V4H7
0 = -10% (-2 mA/-1 V)
1 = +110% (+22 mA/11V)
2 = last measurement
Set switch point relay 2
V5H0
Set fail-safe mode
V5H1
0 = Minimum
1 = Maximum
Set switching hysteresis V5H2
Set status on alarm
V5H3
0 = de-energises
1 = depends on V4H7
Assign relay 2
V5H4
1 = relay 2 on channel 1
Lock parameter matrix
V8H9
Silometer FMC 672 Z/677 Z
Chapter 10: Quick Programming Guide
55