5.1
Linearization for a cylindrical, horizontal tank
This mode is used when you have a cylindrical tank which lies horizontally: the probe
must have a ground tube or the liquid must conduct. The Silometer FMC 672 Z/677 Z
transmitter uses a stored linearization table which requires the entry of the tank diameter
and tank volume for its calculations.
Procedure
Step
Matrix
Entry
Significance
1
V9H5/V3H5/V3H6
Reset and commission transmitter, see Section 4.1.
2
V3H0
e.g. 0
Select units to be used for calibration, 0 = level, 1 = volume
3
-
»E«
Registers entry
4
V2H7
e.g. 10
Enter tank dia. (for level, in units to be used for calibration)
5
-
»E«
Register entry
6
V2H8
e.g. 200
Enter tank volume in the units you require
-
If 100 is entered, the system measures in % vol.
7
-
»E«
Register entry
8
V2H0
1
Select horizontal cylinder mode
9
-
»E«
Press »E« to activate linearization
10
V0H1/V0H2
…
Calibrate, as described in Sections 4.2
…
4.3 or Chapter 8
11
V0H0/V0H9 -
V0H0 indicated volume, V0H9 level before linearization
Note!
•
Omit step 1, transmitter reset, when the second linearization is being entered
•
Channel 2 is linearized at V6H7, V6H8 and V6H0 and calibrated at V4H1 and V4H2
respectively; display at V4H0/V4H9, units selection V7H0.
•
If the calibration is to be in
volume units
(V3H0/V7H0 = 1),
the sequence of steps
must be exactly as shown above
•
When V3H0/V7H0 = 1, the entry at V2H7/V6H7 fixes the end value for the display at
V0H9/V4H9.
BA064E39
Units must correspond to
those used for calibration
Diameter:
V2H7/V6H7
Volume
V2H8/V6H8
M
a
x. m
easuri
n
g
rang
e
0%
10%
20%
90%
100%
level
Volume
»full«
V0H2/V4H2
»empty«
V0H1/V4H1
Fig. 5.2:
Parameters required for
linearization of the Silometer
FMC 672 Z/677 Z for a horizontal
cylinder
Silometer FMC 672 Z/677 Z
Chapter 5: Linearization
28