5 Operation
Proline Prosonic Flow 90
56
Hauser
50
Read assignment of the device
variables to the four process
variables
Access = read
none
Display of the current variable assignment of the
process variables:
– Byte 0: Device variable code for the primary process
variable
– Byte 1: Device variable code for the second process
variable
– Byte 2: Device variable code for the third
process variable
– Byte 3: Device variable code for the fourth
process variable
Factory setting:
• Primary process variable: code 30 for volume flow
• Secondary process variable: code 250 for totalizer
• Third process variable: code 40 for sound velocity
• Fourth process variable: code 49 for flow velocity
!
Note!
You can set or change the assignment of device
variables to process variables using Command 51.
51
Write assignments of the device
variables to the four process
variables
Access = write
Setting of the device variables to the four process
variables:
– Byte 0: Device variable code for the primary process
variable
– Byte 1: Device variable code for the second process
variable
– Byte 2: Device variable code for the third process
variable
– Byte 3: Device variable code for the fourth process
variable
Code of the support device variables:
See data on Page 51
Factory setting:
• Primary proc. variable = Volume flow
• Secondary process variable = Totalizer
• Third process variable = Sound velocity
• Fourth process variable = Flow velocity
The variable assignment of the process variables is
displayed as a response:
– Byte 0: Device variable code for the primary process
variable
– Byte 1: Device variable code for the second process
variable
– Byte 2: Device variable code for the third process
variable
– Byte 3: Device variable code for the fourth process
variable
53
Write device variable unit
Access = write
This command set the unit of the given device
variables. Only those units which suit the device
variable are transferred:
– Byte 0: Device variable code
– Byte 1: HART unit code
Code of the supported device variables:
See data on Page 51
!
Note!
• If the written unit is not the correct one for the
device variable, the device will continue with the
last valid unit.
• If you change the unit of the device variable, this
has no impact on the system units.
The current unit of the device variables is displayed in
the device as a response:
– Byte 0: Device variable code
– Byte 1: HART unit code
!
Note!
Manufacturer-specific units are represented using the
HART unit code “240”.
59
Set number of preambles in
message responses
Access = write
This parameter sets the number of preambles which
are inserts in the message responses:
Byte 0: Number of preambles (2...20)
As a response, the current number of the preambles is
displayed in the response message:
Byte 0: Number of preambles
Command No.
HART command / Access type
Command data
(numeric data in decimal form)
Response data
(numeric data in decimal form)
Содержание Prosonic Flow 90
Страница 4: ...Brief operating instructions Proline Prosonic Flow 90 4 Endress Hauser...
Страница 42: ...4 Wiring Proline Prosonic Flow 90 42 Endress Hauser...
Страница 62: ...5 Operation Proline Prosonic Flow 90 62 Endress Hauser...
Страница 74: ...7 Maintenance Proline Prosonic Flow 90 74 Endress Hauser...
Страница 78: ...8 Accessories Proline Prosonic Flow 90 78 Endress Hauser...
Страница 94: ...9 Trouble shooting Proline Prosonic Flow 90 94 Endress Hauser...
Страница 108: ...10 Technical data Proline Prosonic Flow 90 108 Endress Hauser...
Страница 112: ...Index Proline Prosonic Flow 90 112 Endress Hauser...
Страница 114: ...www endress com worldwide BA068D 06 en 11 04 50099981 FM SGLM6 0...