Proline Prosonic Flow 90
3 Installation
Hauser
15
3.2.3
Orientation
Vertical orientation
Recommended orientation with upward direction of flow (View A). Entrained solids sink down.
Gases rise away from the measuring sensor when fluid is not flowing. The piping can be completely
drained and protected against build-up.
Horizontal orientation
In the recommended installation range in a horizontal installation position (View B), gas and air
accumulation at the pipe cover and problematic build-ups at the bottom of the pipe have a minor
influence on the measurement.
A0001105
Fig. 7:
Installation position (A = vertical, B = horizontal, C = recommended installation range max. 120°)
3.2.4
Inlet and outlet runs (clamp-on version)
If possible, install the sensor well clear of assemblies such as valves, T-pieces, elbows, etc. If several
flow obstructions are installed, the longest inlet or outlet run must be considered. Compliance with
the following requirements for the inlet and outlet runs is recommended to ensure measuring accu-
racy.
A0001106
Fig. 8:
Inlet and outlet runs (clamp-on version)
1 = Valve; 2 = Pump; 3 = Two pipe bends in different directions
A
B
C
C
1
2
3
³
15 x DN
³
5 x DN
³
40 x DN
³
40 x DN
³
20 x DN
Содержание Prosonic Flow 90
Страница 4: ...Brief operating instructions Proline Prosonic Flow 90 4 Endress Hauser...
Страница 42: ...4 Wiring Proline Prosonic Flow 90 42 Endress Hauser...
Страница 62: ...5 Operation Proline Prosonic Flow 90 62 Endress Hauser...
Страница 74: ...7 Maintenance Proline Prosonic Flow 90 74 Endress Hauser...
Страница 78: ...8 Accessories Proline Prosonic Flow 90 78 Endress Hauser...
Страница 94: ...9 Trouble shooting Proline Prosonic Flow 90 94 Endress Hauser...
Страница 108: ...10 Technical data Proline Prosonic Flow 90 108 Endress Hauser...
Страница 112: ...Index Proline Prosonic Flow 90 112 Endress Hauser...
Страница 114: ...www endress com worldwide BA068D 06 en 11 04 50099981 FM SGLM6 0...