3 Installation
Proline Prosonic Flow 90
16
Hauser
3.2.5
Inlet and outlet runs (Insertion version)
If possible, install the sensor well clear of assemblies such as valves, T-pieces, elbows, etc. The long-
est inlet or outlet run must always be taken into account if several flow obstructions are built in.
Compliance with the following requirements for the inlet and outlet runs is recommended to ensure
measuring accuracy.
A0001107
Fig. 9:
Inlet and outlet runs (Insertion version)
1 = Valve; 2 = Pump; 3 = Two pipe bends in different directions
Data above the dimension line: apply to the single path version
Data below the dimension line: apply to the dual path version
3.2.6
Connecting cable length
Shielded cables are offered in the following lengths:
5 m, 10 m, 15 m and 30 m
"
Caution!
Route the cable well clear of electrical machines and switching elements.
1
2
3
³
15 x DN
³
10 x DN
³
5 x DN
³
5 x DN
³
40 x DN
³
40 x DN
³
40 x DN
³
20 x DN
³
20 x DN
³
15 x DN
Содержание Prosonic Flow 90
Страница 4: ...Brief operating instructions Proline Prosonic Flow 90 4 Endress Hauser...
Страница 42: ...4 Wiring Proline Prosonic Flow 90 42 Endress Hauser...
Страница 62: ...5 Operation Proline Prosonic Flow 90 62 Endress Hauser...
Страница 74: ...7 Maintenance Proline Prosonic Flow 90 74 Endress Hauser...
Страница 78: ...8 Accessories Proline Prosonic Flow 90 78 Endress Hauser...
Страница 94: ...9 Trouble shooting Proline Prosonic Flow 90 94 Endress Hauser...
Страница 108: ...10 Technical data Proline Prosonic Flow 90 108 Endress Hauser...
Страница 112: ...Index Proline Prosonic Flow 90 112 Endress Hauser...
Страница 114: ...www endress com worldwide BA068D 06 en 11 04 50099981 FM SGLM6 0...