ProlineйPromagйDй400йHART
Commissioning
Hauser
85
Parameter
Description
User entry / Selection
Factory setting
Assignйfrequencyйoutput
Selectйprocessйvariableйforйfrequencyйoutput. • Off
• Volumeйflow
• Massйflow
• Flowйvelocity
• Electronicйtemperature
Off
Measuringйmodeйoutputй1
Selectйmeasuringйmodeйforйoutput.
• Forwardйflow
• Forward/Reverseйflow
• Reverseйflowйcompensation
Forwardйflow
Measuringйmodeйoutputй1
Selectйmeasuringйmodeйforйoutput.
• Forwardйflow
• Forward/Reverseйflow
• Reverseйflow
• Reverseйflowйcompensation
Forwardйflow
Measuringйmodeйoutputй1
Selectйmeasuringйmodeйforйoutput.
• Forwardйflow
• Forward/Reverseйflow
• Reverseйflow
• Reverseйflowйcompensation
Forwardйflow
10.4.8 Configuring the low flow cut off
Theй
Low flow cut off
йwizardйguidesйyouйsystematicallyйthroughйallйtheйparametersйthat
haveйtoйbeйsetйforйconfiguringйtheйlowйflowйcutйoff.
Navigation
"Setup"йmenuй йLowйflowйcutйoff
Structure of the wizard
Volume flow
Assign variable
Off value
End of wizard
Off
On value
Mass flow
Pres. shock sup.
ййA0020524-EN
31
"Low flow cut off" wizard in the "Setup" menu
Parameter overview with brief description
Parameter
Description
Selection / User entry
Factory setting
Assignйprocessйvariable
Selectйprocessйvariableйforйlowйflowйcutйoff.
• Off
• Volumeйflow
• Massйflow
Volumeйflow
Onйvalueйlowйflowйcutoff
Enterйonйvalueйforйlowйflowйcutйoff.
Signedйfloating-pointйnumber
0йl/h