ProlineйPromagйDй400йHART
Commissioning
Hauser
73
Parameter overview with brief description
Parameter
Description
Selection / User entry
Factory setting
Assignйcurrentйoutput
Selectйprocessйvariableйforйcurrentйoutput.
• Off
• Volumeйflow
• Massйflow
Volumeйflow
Massйflowйunit
Selectйmassйflowйunit.
Result
Theйselectedйunitйappliesйfor:
• Output
• Lowйflowйcutйoff
• Simulationйprocessйvariable
Unitйchooseйlist
Country-specific:
• kg/h
• lb/min
Volumeйflowйunit
Selectйvolumeйflowйunit.
Result
Theйselectedйunitйappliesйfor:
• Output
• Lowйflowйcutйoff
• Simulationйprocessйvariable
Unitйchooseйlist
Country-specific:
• l/h
• gal/minйсus)
Densityйunit
Selectйdensityйunit.
Result
Theйselectedйunitйappliesйfor:
• Output
• Simulationйprocessйvariable
• Densityйadjustmentйсinй
Expert
йmenu)
Unitйchooseйlist
Country-specific:
• kg/l
• lb/ft³
Fixedйdensity
Enterйfixedйvalueйforйmediumйdensity.
0.01йtoй15
й
000йkg/m³
1
й
000йkg/m³
Currentйspan
Selectйcurrentйrangeйforйprocessйvalueйoutput
andйupper/lowerйlevelйforйalarmйsignal.
• 4...20йmAйNAMUR
• 4...20йmAйUS
• 4...20йmA
• 0...20йmA
• Fixedйcurrent
4...20йmAйNAMUR
0/4йmAйvalue
Enterй4йmAйvalue.
Signedйfloating-pointйnumber
0йl/h
20йmAйvalue
Enterй20йmAйvalue.
Signedйfloating-pointйnumber
0.025йl/h
Failureйmode
Defineйoutputйbehaviorйinйalarmйcondition.
• Min.
• Max.
• Lastйvalidйvalue
• Actualйvalue
• Definedйvalue
Max.
Failureйcurrent
Enterйcurrentйoutputйvalueйinйalarm
condition.
3.59
-3
йtoй22.5
-3
йmA
22.5йmA
10.4.4 Configuring the pulse/frequency/switch output
Theй
Pulse/frequency/switch output 1 to 2
йsubmenuйguidesйyouйsystematicallyйthrough
allйtheйparametersйthatйcanйbeйsetйforйconfiguringйtheйselectedйoutputйtype.
Pulse output
Navigation
"Setup"йmenuй йPulse/frequency/switchйoutputй1йtoй2
Содержание Proline Promag D 400 HART