ProlineйPromagйDй400йHART
Electricalйconnection
Hauser
31
Capacitance: core/shield
≤420йpF/mйс128йpF/ft)
Operating temperature
–20йtoй+80й°Cйс–68йtoй+176й°F)
Coil current cable
Standard cable
2й×0.75йmm
2
йс18йAWG)йwithйcommon,йbraidedйcopperйshieldйс й
~
й7йmmйс0.28"))
andйindividuallyйshieldedйcores
Conductor resistance
≤37йΩ/kmйс0.011йΩ/ft)
Capacitance: core/core,
shield grounded
≤120йpF/mйс37йpF/ft)
Operating temperature
–20йtoй+80й°Cйс–68йtoй+176й°F)
Test voltage for cable
insulation
≤йACй1433йVйr.m.s.й50/60йHzйorй≥йDCй2026йV
1
2
3
4
5
6
7
a
b
ййA0003194
9
Cable cross-section
a
Electrode cable
b
Coil current cable
1
Core
2
Core insulation
3
Core shield
4
Core jacket
5
Core reinforcement
6
Cable shield
7
Outer jacket
Operation in zones of severe electrical interference
Theйmeasuringйsystemйmeetsйtheйgeneralйsafetyйrequirementsйс ййй141)йandйEMC
specificationsйс ййй133).
Groundingйisйbyйmeansйofйtheйgroundйterminalйprovidedйforйtheйpurposeйinsideйthe
connectionйhousing.йTheйstrippedйandйtwistedйlengthsйofйcableйshieldйtoйtheйground
terminalйmustйbeйasйshortйasйpossible.
Cable diameter
• Cableйglandsйsupplied:
– Forйstandardйcable:йM20й×й1.5йwithйcableй 6йtoй12йmmйс0.24йtoй0.47йin)
– Forйreinforcedйcable:йM20й×й1.5йwithйcableй 9.5йtoй16йmmйс0.37йtoй0.63йin)
• сPlug-in)йspringйterminalsйforйwireйcross-sectionsй0.5йtoй2.5йmm
2
йс20йtoй14йAWG)