10.4.9 Configuring empty pipe detection
Theй
Empty pipe detection
йwizardйguidesйyouйsystematicallyйthroughйallйtheйparameters
thatйhaveйtoйbeйsetйforйconfiguringйtheйlowйflowйcutйoff.
Navigation
"Setup"йmenuй йEmptyйpipeйdetection
Structure of the wizard
Empty pipe det.
Response time
End of wizard
New adjustment
Cancel
Empty pipe adj.
Progress
Full pipe adjust.
Ok
Busy
Not ok
On
Switch point EPD
Off
ййA0017210-EN
32
"Empty pipe detection" wizard in the "Setup" menu
Parameter overview with brief description
Parameter
Description
Selection / User interface /
User entry
Factory setting
Emptyйpipeйdetection
Switchйemptyйpipeйdetectionйonйandйoff.
• Off
• On
Off
Newйadjustment
Selectйtypeйofйadjustment.
• Cancel
• Emptyйpipeйadjust
• Fullйpipeйadjust
Cancel
Progress
• Ok
• Busy
• Notйok
Switchйpointйemptyйpipeйdetection
Enterйhysteresisйinй%,йbelowйthisйvalueйthe
measuringйtubeйwillйdetectedйasйempty.
0йtoй100й%
50й%
Responseйtimeйemptyйpipeйdetection Enterйtheйtimeйbeforeйdiagnosticйmessage
S862йррPipeйemptyррйisйdisplayedйforйempty
pipeйdetection.
0йtoй100йs
1йs