Tankside Monitor NRF81

Tank Gauging

BA01465G/00/EN/03.18

71406899

2018-06-07
01.02.zz (Device firmware)

Содержание NRF81

Страница 1: ...Products Solutions Services Operating Instructions Tankside Monitor NRF81 Tank Gauging BA01465G 00 EN 03 18 71406899 2018 06 07 01 02 zz Device firmware...

Страница 2: ...Tankside Monitor NRF81 2 Endress Hauser Order code Ext ord cd Ser no www endress com deviceviewer Endress Hauser Operations App XXXXXXXXXXXX XXXXX XXXXXX XXX XXXX XX Serial number 1 3 2 A0023555...

Страница 3: ...a Tankvision Tank Scanner NXA820 and FieldCare 50 8 System integration 53 8 1 Overview of the Device Description files DTM 53 9 Commissioning 54 9 1 Initial settings 54 9 2 Configuring the tank gaugin...

Страница 4: ...s situation can result in serious or fatal injury CAUTION CAUTION This symbol alerts you to a dangerous situation Failure to avoid this situation can result in minor or medium injury NOTICE NOTE This...

Страница 5: ...processes or actions that are permitted Preferred Procedures processes or actions that are preferred Forbidden Procedures processes or actions that are forbidden Tip Indicates additional information R...

Страница 6: ...on hazardous area Indicates the non hazardous area 1 2 6 Symbols at the device Symbol Meaning Safety instructions Observe the safety instructions contained in the associated Operating Instructions Tem...

Страница 7: ...uctions BA The Operating Instructions contain all the information that is required in various phases of the life cycle of the device from product identification incoming acceptance and storage to moun...

Страница 8: ...ia Ga IIC T6 Gb XA01531G FD FM C US XP AIS Cl I Div 1 Gr BCD T6 AEx d ia IIC T6 XA01532G GA EAC Ex db ia Ga IIC T6 Gb in preparation IA IEC Ex db ia Ga IIC T6 Gb XA01531G KA KC Ex db ia Ga IIC T6 Gb...

Страница 9: ...1 About this document Endress Hauser 9 1 4 Registered trademarks FieldCare Registered trademark of the Endress Hauser Process Solutions AG Reinach Switzerland MODBUS Registered trademark of the MODBUS...

Страница 10: ...trinsically safe i s or explosion proof XP power to the connected sensors on the tank Various industry standard digital gauging communication protocols support integration into open architecture tank...

Страница 11: ...To eliminate a danger for persons or for the facility when the device is used in the hazardous area e g explosion protection pressure vessel safety Based on the nameplate check whether the ordered de...

Страница 12: ...F81 12 Endress Hauser 3 Product description 3 1 Product design 1 2 3 A0027767 1 Design of Tankside Monitor NRF81 1 Housing 2 Display and operating module can be operated without opening the cover 3 Mo...

Страница 13: ...he measuring device Nameplate specifications Extended order code with breakdown of the device features on the delivery note Enter serial numbers from nameplates in W M Device Viewer www endress com de...

Страница 14: ...nded order code 5 Supply voltage 6 Thread for cable entry 7 Device ID 8 Firmware version 9 Device revision 10 Metrology certification numbers 11 Customized parametrization data 12 Ambient temperature...

Страница 15: ...to 80 C 58 to 176 F Store the device in its original packaging 4 3 2 Transport NOTICE Risk of injury Transport the measuring device to the measuring point in its original packaging Take into account t...

Страница 16: ...ng 150 5 9 150 5 9 13 5 0 53 M12 15 Nm 11 06 lbf A0029901 3 Wall mounting of the Tankside Monitor 5 1 2 Pipe mounting Ordering feature 620 Accessory enclosed Mounting kit PV Mounting kit pipe DN32 50...

Страница 17: ...ection m Does the device conform to the measuring point specifications For example Process temperature Process pressure refer to the chapter on Material load curves of the Technical Information docume...

Страница 18: ...or I O modules Up to four I O modules depending on the order code Modules with four terminals can be in any of these slots Modules with eight terminals can be in slot B or C The exact assignment of th...

Страница 19: ...nameplate 6 1 2 HART Ex i IS interface D E F C B A 1 1 1 1 3 2 2 4 1 HR CDI WP on SIM 2 2 3 3 4 4 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 i E 1 1 2 CDI i G 1 3 2 POWER 3 A0033414 E1 H E2 H 3 Orange LED indica...

Страница 20: ...these slots contain different I O modules The table below shows which module is located in which slot for a specific device version The slot assignment for the device is also indicated on a label atta...

Страница 21: ...odbus Analog Ex d XP Digital Digital A1 A1 B1 Modbus Modbus Analog Ex d XP A1 A1 B2 Modbus Modbus Analog Ex d XP Digital A1 A2 X0 Modbus Analog Ex d XP Analog Ex d XP A1 A2 A1 Modbus Analog Ex d XP An...

Страница 22: ...tal B1 A1 A2 V1 Analog Ex d XP Digital Digital B1 A1 B1 V1 Modbus Analog Ex d XP B1 A1 B2 V1 Modbus Analog Ex d XP Digital B1 A2 X0 V1 Analog Ex d XP Analog Ex d XP B1 A2 A1 V1 Analog Ex d XP Analog E...

Страница 23: ...g Ex d XP Digital Digital E1 X0 B1 Modbus Analog Ex d XP E1 X0 B2 Modbus Analog Ex d XP Digital E1 X0 B3 Modbus Analog Ex d XP Digital Digital E1 A1 X0 Analog Ex d XP Analog Ex d XP E1 A1 A1 Analog Ex...

Страница 24: ...g Ex i IS Digital Digital H1 X0 B1 Modbus Analog Ex i IS H1 X0 B2 Modbus Analog Ex i IS Digital H1 X0 B3 Modbus Analog Ex i IS Digital Digital H1 A1 X0 Analog Ex i IS Analog Ex d XP H1 A1 A1 Analog Ex...

Страница 25: ...ces are designated by the respective slot and the terminals within this slot A1 4 B1 4 C1 4 D1 4 Terminals of the Modbus module Terminal 1 Name Description X1 S Cable shielding connected via a capacit...

Страница 26: ...4 4 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 POWER i B 1 2 3 4 5 6 7 8 B1 3 B4 8 C 1 2 3 4 5 6 7 8 C1 3 C4 8 A0031168 Terminals Function Connection diagrams Designation in the operating menu B1 3 Analog input...

Страница 27: ...7 8 8 i G 1 3 2 POWER c a b E G F 1 1 1 3 2 2 4 HR CDI WP on SIM i D C B A 1 1 2 2 3 3 4 4 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 G 1 3 2 POWER A0027931 8 Passive usage of the Analog I O module in the outpu...

Страница 28: ...I WP on SIM 2 2 3 3 4 4 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 i G 1 3 2 POWER a E G F 1 1 1 3 2 2 4 HR CDI WP on SIM i D C B A 1 1 2 2 3 3 4 4 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 G 1 3 2 POWER b A0027934 10 Pas...

Страница 29: ...2 5 V 22 mA Operating mode 4 20mA output or HART slave 4 20mA output D E F C B A 1 1 1 1 3 2 2 4 1 HR CDI WP on SIM 2 2 3 3 4 4 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 i G 1 3 2 POWER b a E G F 1 1 1 3 2 2 4...

Страница 30: ...4 4 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 G 1 3 2 POWER a A0027936 13 Active usage of the Analog I O module in the HART master mode a Up to 6 external devices with HART signal output The maximum current con...

Страница 31: ...A 1 1 1 1 3 2 2 4 1 HR CDI WP on SIM 2 2 3 3 4 4 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 i G 1 3 2 POWER A0027717 14 Connection of a Micropilot S FMR5xx to the Analog input module of a Tankside Monitor NRF81...

Страница 32: ...nputs or outputs examples Each Digital IO Module provides two digital inputs or outputs In the operating menu each input or output is designated by the respective slot and two terminals within this sl...

Страница 33: ...11 AWG Power supply line Standard device cable is sufficient for the power line HART communication line Standard device cable is sufficient if only the analog signal is used Shielded cable is recomme...

Страница 34: ...trap A0013960 5 Insert blind plugs appropriate for the safety rating of the device e g Ex d XP 6 4 Post connection check m Are cables or the device undamaged visual inspection m Do the cables comply w...

Страница 35: ...an be accessed by the following interfaces The display and operating module at the device local operation 37 FieldCare connected through the service interface in the terminal compartment of the device...

Страница 36: ...ror messages Device information Contains information needed to identify the device Simulation Used to simulate measured values or output values Expert 1 Contains all parameters of the device including...

Страница 37: ...e device status in the standard view Other views are used to navigate through the operating menu and to set parameter values The device is operated by three optical keys namely and E They are actuated...

Страница 38: ...ied out by the user e g level outside configured span A0013957 Maintenance required Maintenance is required The measured value is still valid Measured value status symbols Symbol Meaning A0012102 Stat...

Страница 39: ...6 Enter key Pressing the key briefly opens the operating menu Pressing the key for 2 s opens the context menu Level visible if the keylock is inactive Shows the measured levels Keylock on visible if t...

Страница 40: ...eration in the header if you are in the Operation menu A0011974 Setup Is displayed in the main menu next to the selection Setup in the header if you are in the Setup menu A0011976 Expert Is displayed...

Страница 41: ...ing the key briefly opens the selected menu submenu or parameter For parameters Pressing the key for 2 s opens the help text for the function of the parameter if present A0028327 Escape key combinatio...

Страница 42: ...avigation Wizard navigation symbols Symbol Meaning A0013972 Parameters within a wizard A0013978 Switches to the previous parameter A0013976 Confirms the parameter value and switches to the next parame...

Страница 43: ...ion to the left A0013986 Exits the input without applying the changes A0014040 Clears all entered characters Meaning of the keys in the numeric editor Key Meaning A0028324 Minus key In the input mask...

Страница 44: ...ase letters For entering numbers For entering special characters A0013985 Confirms selection A0013987 Switches to the selection of the correction tools A0013986 Exits the input without applying the ch...

Страница 45: ...7 Keypad lock Automatic keypad lock Operation via the local display is automatically locked after a start up or restart of the device if the device has not been operated via the display for 1 minute...

Страница 46: ...Define access code Define access code 2 Enter the intended access code max 4 digits 3 Repeat the same code in the Confirm access code parameter The user is in the Operator role The symbol appears in...

Страница 47: ...ule with a gentle rotation movement 4 Using a flat blade screwdriver or a similar tool set the write protection switch WP into the desired position ON operating menu is locked OFF operating menu is un...

Страница 48: ...382 Indication of the locking state XXXX XXX X X 20 50 XX XX A0015870 22 Write protection symbol in the header of the display Write protection via locking switch is indicated as follows Locking status...

Страница 49: ...ace 2 Commubox FXA291 3 Computer with FieldCare operating tool and CDI Communication FXA291 COM DTM The Save Restore function After a device configuration has been saved to a computer and restored to...

Страница 50: ...d FieldCare 7 5 1 Wiring scheme NXA820 5 6 4 1 2 3 7 A0025621 24 Connection of Tank Gauging devices to FieldCare via the Tankvision Tank Scanner NXA820 1 Proservo NMS8x 2 Tankside Monitor NRF81 3 Micr...

Страница 51: ...ure the HART CommDTM NXA is installed and update the DTM catalogue if required 2 Create a new project in FieldCare 3 A0028515 Add a new device NXA HART Communication 4 A0028516 Open the configuration...

Страница 52: ...The device can be configured The Save Restore function After a device configuration has been saved to a computer and restored to the device using the Save Restore function of FieldCare the device must...

Страница 53: ...w of the Device Description files DTM To integrate the device via HART into FieldCare a Device Description file DTM according to the following specification is required Manufacturer ID 0x11 Device typ...

Страница 54: ...dvanced setup Display Language 2 Select the display language This setting only affects the language on the display module To set the language in the operating tool use the language setting functionali...

Страница 55: ...ioning Endress Hauser 55 3 Use the following parameters to set the date and time Year Month Day Hour Minutes 4 Go to the Set date parameter and select the Confirm time option The real time clock is se...

Страница 56: ...Description Linking input values to tank variables 66 Tank calculation Direct Level Measurement 67 Tank calculation Hybrid Tank Measurement System HTMS 68 Tank calculation Hydrostatic Tank Gauging HT...

Страница 57: ...ing mode of the Analog I O module This section is not relevant for the HART Ex is output Slot E This output always functions as a HART master for the connected HART slaves If HART devices are connecte...

Страница 58: ...There is a submenu for each connected HART device 2 For each device go to the corresponding submenu 3 If the device measures a pressure Go to the Output pressure parameter 128 and specify which of th...

Страница 59: ...Tankside Monitor NRF81 Commissioning Endress Hauser 59 2 Select the HART device to be removed This procedure is also necessary if a defective device is exchanged...

Страница 60: ...ect Yes 3 Go to the Bottom point parameter and enter the position of the bottom temperature element see picture below a A0030099 26 Position of the bottom temperature element a Distance from bottom te...

Страница 61: ...3 3 Go to the Operating mode parameter 138 and select 4 20mA input or HART master 4 20mA input 4 Go to the Process variable parameter 144 and specify which process variable is transmitted by the conn...

Страница 62: ...I O module Setup Advanced setup Input output Analog IP X4 8 3 Go to the RTD type parameter 132 and specify the type of the connected RTD 4 A C B 1 1 1 2 2 2 3 3 3 4 4 4 5 5 5 6 6 6 7 7 7 8 8 8 A002637...

Страница 63: ...mines whether the measured temperature refers to the product or to the gas phase Offset for resistance and or temperature An offset for the resistance or the temperature can be defined in the followin...

Страница 64: ...portant parameters of this submenu are Operating mode and Contact type The Operating mode parameter Setup Advanced setup Input output Digital Xx x Operating mode DIO 2 4 _ 2 4 1 3 1 3 A DIO B A0029262...

Страница 65: ...Normally open Contact type Normally closed Open Inactive Active Closed Active Inactive Behavior in special situaions During start up Unknown Unknown Fault in measurement Error Error The internal state...

Страница 66: ...urce Setup Advanced setup Application Tank configuration Temperature Liquid temp source Temperature of the air surrounding the tank Setup Advanced setup Application Tank configuration Temperature Air...

Страница 67: ...l measurement without temperature B Direct level and temperature measurement 1 Level transmitter typically FMR540 or FMR51 2 Tankside Monitor 3 To inventory management system 4 Temperature transmitter...

Страница 68: ...tem 4 Pressure sensor bottom 5 Pressure sensor top 1 Navigate to Setup Advanced setup Application Tank configuration Level 2 Go to Level source 122 and specify from which device the level is obtained...

Страница 69: ...anced setup Application Tank configuration Pressure P2 middle HP1 P2 Distance between P1 and P2 sensors Setup Advanced setup Application Tank configuration Pressure P1 2 distance P3 Top pressure Setup...

Страница 70: ...es the actual pressure at the P1 position If necessary the indicated pressure can be corrected by the P1 offset parameter 4 Go to the P1 position parameter 182 and enter the distance from the datum pl...

Страница 71: ...4 Go to the P3 position parameter 186 and enter the distance from the datum plate to the P3 sensor 5 Go to the P3 abs rel parameter 186 and specify whether the P3 sensor measures an absolute or a rel...

Страница 72: ...e compensation is based on a linear approximation obtained from manual hand dips at several levels divided over the full range of the tank A B C D A0028721 33 Correction of the hydrostatic tank deform...

Страница 73: ...sed on manual or measured values and the temperature of the shell when the tank was calibrated for details refer to API MPMS Chapter 12 1 This correction is recommended for the following situations if...

Страница 74: ...A B 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 9 10 10 A0029539 34 Principle of the limit evaluation A Alarm mode On B Alarm mode Latching 1 HH alarm value 2 H alarm value 3 L alarm value 4 LL alarm value 5 HH...

Страница 75: ...put source parameter and select the tank variable which is to be transmitted via the 4 20mA output 4 Go to the 0 value parameter and enter the value of the selected tank variable which will be mapped...

Страница 76: ...HART variables are transmitted to a connected HART Master Special case PV 4 20mA signal In exceptional cases it might be required that the Primary Variable PV transmits a different tank variable than...

Страница 77: ...the assigned tank variable is not yet available the output current assumes the defined errror value The PV mA selector parameter does not influence the output current at the terminals of the Analog I...

Страница 78: ...sible locations of the Modbus modules examples depending on the device version these modules may also be in slot B or C 20 The Tankside Monitor NRF81 acts as a Modbus slave Measured or calculated tank...

Страница 79: ...3 4 A1 4 i D 1 2 3 4 D1 4 A0031200 39 Possible locations of the V1 modules examples depending on the device version these modules may also be in slot B or C 20 The following submenus are used to conf...

Страница 80: ...nals within this slot The most important parameters of this submenu are Operating mode Digital input source and Contact type A digital output can be used to output the state of an alarm if an alarm ha...

Страница 81: ...e Open Closed Active Closed Open For SIL applications Contact type is automatically set to Normally closed by the device when starting the SIL confirmation procedure In case of a power supply failure...

Страница 82: ...tem it is possible to simulate different situations measured values diagnostic messages etc See the Simulation submenu 244 for details 9 5 Protecting settings from unauthorized access There are two po...

Страница 83: ...the SIL Safety manual CT active all parameters The custody transfer mode is active 47 WHG locked in preparation The device is in WHG locked mode in preparation Temporarily locked Write access to the...

Страница 84: ...le is not connected correctly Connect the plug correctly Display is defective Replace display Display contrast too low Set Setup Advanced setup Display Contrast display to a value 60 Communication err...

Страница 85: ...g elements Status signals A0013956 Failure A device error is present The measured value is no longer valid A0013959 Function check The device is in service mode e g during a simulation or a warning A0...

Страница 86: ...cs event Diagnostics event Status symbol Status signal Event number Event text Example A0013962 A0013956 441 Curr output 1 3 digit number If two or more diagnostic messages are pending simultaneously...

Страница 87: ...tic code 5 Operation time of occurrence 6 Remedial measures A diagnostic message appears in the standard view measured value display 1 Press symbol The Diagnostic list submenu opens 2 Select the desir...

Страница 88: ...99 EN 1 Status area with status signal 2 Diagnostic information 3 Remedial measures with Service ID Furthermore diagnostic events that have occurred can be viewed in the Diagnostic list submenu 11 3 1...

Страница 89: ...quickly On the home page Remedy information is displayed in a separate field below the diagnostics information In the Diagnostics menu Remedy information can be called up in the working area of the us...

Страница 90: ...or main electronics F Alarm 262 Module connection 1 Check module connections 2 Change electronic modules F Alarm 270 Main electronic failure Replace main electronics F Alarm 271 Main electronic failu...

Страница 91: ...t AIO 1 to 2 1 Check wiring 2 Change I O module F Alarm 408 Invalid range AIO 1 to 2 1 Check device configuration 2 Check wiring C Warning 409 RTD temp out of range 1 to 2 1 Check electronic modules 2...

Страница 92: ...lid Change input source C Warning 507 Liquid temp source no longer valid Change input source C Warning 508 Vapor temperatur source no longer valid Change input source C Warning 509 Air temperature sou...

Страница 93: ...ce C Warning 539 Modbus A1 4 SP source invalid Set valid SP input selector C Warning 540 Modbus B1 4 SP source invalid Set valid SP input selector C Warning 541 Modbus C1 4 SP source invalid Set valid...

Страница 94: ...t source C Warning 570 V1 A1 4 analog source invalid Set valid analog input selector C Warning 571 V1 B1 4 analog source invalid Set valid analog input selector C Warning 572 V1 C1 4 analog source inv...

Страница 95: ...C1 4 percent source invalid Set valid percentage input selector C Warning 593 Modbus D1 4 percent source invalid Set valid percentage input selector C Warning 594 V1 A1 4 percent source invalid Set va...

Страница 96: ...iagnostic event M Warning 961 Alarm 1 to 4 HighHigh 1 Check level 2 Check configuration settings C Warning 962 Alarm 1 to 4 High 1 Check level 2 Check configuration settings C Warning 963 Alarm 1 to 4...

Страница 97: ...ages can be displayed If more than 5 messages are pending the messages with the highest priority are shown on the display Navigation path Diagnostics Diagnostic list Calling up and closing the remedia...

Страница 98: ...oftware version of the individual modules etc can be found in the Device information submenu 241 11 8 Firmware history Date Software version Modifications Documentation NRF81 Operating Instructions De...

Страница 99: ...leaning the exterior of measuring devices always use cleaning agents that do not attack the surface of the housing or the seals 12 2 Endress Hauser services Endress Hauser offers a wide variety of ser...

Страница 100: ...y Endress Hauser Service may convert a certified device into a different certified variant Document all repair work and conversions 13 1 3 Replacement of a device or electronic module After a complete...

Страница 101: ...delivered or ordered Legal specifications require Endress Hauser as an ISO certified company to follow certain procedures when handling products that are in contact with the medium To ensure safe swif...

Страница 102: ...A0028479 43 Weather protection cover dimensions mm in Materials Part Material Protection cover and mounting brackets 316L 1 4404 Screws and washers A4 The weather protection cover can be ordered toget...

Страница 103: ...cts Endress Hauser field devices with CDI interface Endress Hauser Common Data Interface to the USB interface of a computer For details refer to Technical Information TI00405C Accessory Description Fi...

Страница 104: ...version and parametrization some parameters will not be available in a given situation For details refer to the Prerequisite category in the description of the respective parameter The representation...

Страница 105: ...nt position 115 Element position 1 to 24 115 Density 116 Observed density 116 Vapor density 116 Air density 116 Measured upper density 117 Measured middle density 117 Measured lower density 117 Pressu...

Страница 106: ...4 Locking status 124 Access status tooling 124 Enter access code 124 Input output 125 HART devices 125 Number of devices 125 HART Device s 126 Forget device 131 Analog IP 132 Operating mode 132 RTD ty...

Страница 107: ...Current span 139 Fixed current 140 Analog input source 140 Failure mode 141 Error value 142 Input value 142 0 value 142 100 value 143 Input value 143 Output values 143 Process variable 144 Analog inp...

Страница 108: ...ut value 150 Contact type 150 Output simulation 150 Output values 151 Readback value 151 Used for SIL WHG 152 Communication 153 Communication interface 1 to 2 Communication interface protocol 153 Conf...

Страница 109: ...HTG 206 HTMS 211 Alarm Alarm 1 to 4 215 Display 223 Language 223 Format display 223 Value 1 to 4 display 224 Decimal places 1 to 4 225 Separator 225 Number format 226 Header 226 Header text 226 Displa...

Страница 110: ...e time 232 Set date 232 Year 232 Month 233 Day 233 Hour 233 Minute 234 SIL confirmation 235 Deactivate SIL WHG 235 Administration 236 Define access code 236 Device reset 236 Diagnostics 237 Actual dia...

Страница 111: ...vice information 241 Device tag 241 Serial number 241 Firmware version 241 Firmware CRC 241 Weight and measures configuration CRC 242 Device name 242 Order code 242 Extended order code 1 to 3 242 Simu...

Страница 112: ...distance from the zero position tank bottom or datum plate to the product surface Additional information Read access Operator Write access Tank Level Navigation Operation Level Tank Level Description...

Страница 113: ...on tank bottom or datum plate Value is updated when device generates a valid Interface measurement Additional information Read access Maintenance Write access Lower interface level Navigation Operatio...

Страница 114: ...eration Temperature Air temperature Navigation Operation Temperature Air temperature Description Shows the air temperature Additional information Read access Operator Write access Liquid temperature N...

Страница 115: ...ent temperature Element temperature 1 to 24 Navigation Operation Temperature NMT element values Element temperature Element temperature 1 to 24 Description Shows the temperature of an element in the N...

Страница 116: ...rator Write access This value is calculated from different measured variables depending on the selected calculation method 188 Vapor density Navigation Operation Density Vapor density Description Defi...

Страница 117: ...ows the density of the upper phase Additional information Read access Operator Write access Measured middle density Navigation Operation Density Measured middle density Description Density of the midd...

Страница 118: ...he tank bottom Additional information Read access Operator Write access P2 middle Navigation Operation Pressure P2 middle Description Shows the pressure P2 at the middle transmitter Additional informa...

Страница 119: ...access Maintenance GP Value 1 Navigation Operation GP values GP Value 1 Description Displays the value that will be used as general purpose value Additional information Read access Operator Write acc...

Страница 120: ...Hauser Additional information Read access Operator Write access GP Value 4 Navigation Operation GP values GP Value 4 Description Displays the value that will be used as general purpose value Addition...

Страница 121: ...Navigation Setup Units preset Description Defines a set of units for length pressure and temperature Selection mm bar C m bar C mm PSI C ft PSI F ft in 16 PSI F ft in 8 PSI F Customer value Factory s...

Страница 122: ...ation Setup Tank level Description Shows the distance from the zero position tank bottom or datum plate to the product surface Additional information Read access Operator Write access Level source Nav...

Страница 123: ...id temp source Description Defines source from which the liquid temperature is obtained Selection Manual value HART device 1 15 temperature AIO B1 3 value AIO C1 3 value AIP B4 8 value AIP C4 8 value...

Страница 124: ...ditional information Read access Operator Write access Access status tooling Navigation Setup Advanced setup Access status tooling Description Shows the access authorization to the parameters via the...

Страница 125: ...setup Input output HART devices submenu Navigation Setup Advanced setup Input output HART devices Number of devices Navigation Setup Advanced setup Input output HART devices Number of devices Descript...

Страница 126: ...me Description Shows the name of the transmitter Additional information Read access Operator Write access Polling address Navigation Setup Advanced setup Input output HART devices HART Device s Pollin...

Страница 127: ...V QV Additional information Read access Operator Write access Maintenance Communication status Navigation Setup Advanced setup Input output HART devices HART Device s Communication status Description...

Страница 128: ...ART devices other than NMT Operating mode 127 PV SV TV QV Description Shows the third HART variable TV Additional information Read access Operator Write access blank HART QV designation dependent on d...

Страница 129: ...ured variables are allocated automatically Description Defines which HART variable is the density Selection No value Primary variable PV Secondary variable SV Tertiary variable TV Quaternary variable...

Страница 130: ...tion No value Primary variable PV Secondary variable SV Tertiary variable TV Quaternary variable QV Factory setting No value Additional information Read access Operator Write access Maintenance Output...

Страница 131: ...d setup Input output HART devices Forget device Forget device Description With this function an offline device can be deleted from the device list Selection HART Device 1 HART Device 2 HART Device 3 H...

Страница 132: ...6 7 8 C 1 2 3 4 5 6 7 8 C1 3 C4 8 A0032465 44 Terminals for the Analog IP submenu B4 8 or C4 8 respectively Navigation Setup Advanced setup Input output Analog IP Operating mode Navigation Setup Advan...

Страница 133: ...g Pt100 385 a 0 00385 IEC751 Additional information Read access Operator Write access Maintenance RTD connection type Navigation Setup Advanced setup Input output Analog IP RTD connection type Prerequ...

Страница 134: ...evel linearized Additional information Read access Operator Write access Maintenance 0 value Navigation Setup Advanced setup Input output Analog IP 0 value Prerequisite Operating mode 132 4 20mA input...

Страница 135: ...dvanced setup Input output Analog IP Minimum probe temperature Prerequisite Operating mode 132 RTD temperature input Description Minimum approved temperature of the connected probe If the temperature...

Страница 136: ...parameter in conjunction with the measured level determines whether the temperature probe is still covered by the product If this is no longer the case the status of the temperature value will be inv...

Страница 137: ...urrent Navigation Setup Advanced setup Input output Analog IP Gauge current Prerequisite Operating mode 132 Gauge power supply Description Shows the current on the power supply line for the connected...

Страница 138: ...r C1 3 respectively Navigation Setup Advanced setup Input output Analog I O Operating mode Navigation Setup Advanced setup Input output Analog I O Operating mode Description Defines the operating mode...

Страница 139: ...T devices 24 mA i e 4 mA per device if 6 devices are connected Output voltage of the Ex d module 17 0 V 4 mA to 10 5 V 22 mA Output voltage of the Ex ia module 18 5 V 4 mA to 12 5 V 22 mA Current span...

Страница 140: ...xed current Description Defines the fixed output current User entry 4 to 22 5 mA Factory setting 4 mA Additional information Read access Operator Write access Maintenance Analog input source Navigatio...

Страница 141: ...V 5 HART device 1 15 SV 5 HART device 1 15 TV 5 HART device 1 15 QV 5 Factory setting Tank level Additional information Read access Operator Write access Maintenance Failure mode Navigation Setup Adva...

Страница 142: ...log I O Input value Prerequisite Operating mode 138 4 20mA output or HART slave 4 20mA output Current span 139 Fixed current Description Shows the input value of the analog I O module Additional infor...

Страница 143: ...erator Write access Maintenance Input value Navigation Setup Advanced setup Input output Analog I O Input value Prerequisite Operating mode 138 4 20mA output or HART slave 4 20mA output Current span 1...

Страница 144: ...alue Navigation Setup Advanced setup Input output Analog I O Analog input 0 value Prerequisite Operating mode 138 4 20mA input or HART master 4 20mA input Description Value corresponding to an input c...

Страница 145: ...Factory setting Warning Additional information Read access Operator Write access Maintenance Process value Navigation Setup Advanced setup Input output Analog I O Process value Prerequisite Operating...

Страница 146: ...log I O Damping factor Prerequisite Operating mode 138 Disabled or HART master Description Defines the damping constant in seconds User entry 0 to 999 9 s Factory setting 0 s Additional information Re...

Страница 147: ...ected SIL WHG chain Navigation Setup Advanced setup Input output Analog I O Expected SIL WHG chain Prerequisite Operating mode 138 4 20mA output or HART slave 4 20mA output The device has a SIL approv...

Страница 148: ...ates any of these submenus The structure of all these submenus is the same D E F C B A 1 1 1 1 3 2 2 4 1 HR CDI WP on SIM 2 2 3 3 4 4 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 POWER A 1 2 3 4 A1 2 A3 4 i C 1 2...

Страница 149: ...igh Alarm x High or HighHigh Alarm x Low Alarm x LowLow Alarm x Low or LowLow Digital Xx x Pri Modbus x Sec Modbus x Factory setting None Additional information Meaning of the options Alarm x any Alar...

Страница 150: ...equisite Operating mode 148 Disabled Description Determines the switching behavior of the input or output Selection Normally open Normally closed Factory setting Normally open Output simulation Naviga...

Страница 151: ...ulating inactive Open Open Open Fault 1 Closed Open Open Fault 2 Open Closed Open The Fault 1 and Fault 2 options can be used to check the correct switching behavior of the two relays Output value Nav...

Страница 152: ...n Setup Advanced setup Input output Digital Xx x Used for SIL WHG Prerequisite Operating mode 148 Output passive The device has a SIL certificate Description Determines whether the discrete I O module...

Страница 153: ...ation of the Modbus or V1 modules examples depending on the device version these modules may also be in slot B or C Navigation Setup Advanced setup Communication Modbus X1 4 or V1 X1 4 submenu This su...

Страница 154: ...scription Defines the baud rate of the Modbus communication Selection 300 BAUD 1200 BAUD 2400 BAUD 4800 BAUD 9600 BAUD 19200 BAUD Factory setting 9600 BAUD Additional information Read access Operator...

Страница 155: ...dbus X1 4 Configuration Float swap mode Prerequisite Communication interface protocol 153 MODBUS Description Sets the format of how the floating point value is transfered on Modbus Selection Normal 3...

Страница 156: ...Operating menu Tankside Monitor NRF81 156 Endress Hauser Factory setting Off Additional information Read access Operator Write access Maintenance...

Страница 157: ...ection None V1 Factory setting None Additional information Read access Operator Write access Maintenance V1 address Navigation Setup Advanced setup Communication V1 X1 4 Configuration V1 address Prere...

Страница 158: ...erface protocol 153 V1 Description Determines the transmittable range of levels Selection ve ve ve Factory setting ve Additional information Read access Operator Write access Maintenance In V1 the lev...

Страница 159: ...tion interface protocol 153 V1 Description Adjusts the impedance of the communication line User entry 0 to 15 Factory setting 15 Additional information Read access Operator Write access Maintenance Th...

Страница 160: ...1 4 any Alarm 1 4 HighHigh Alarm 1 4 High or HighHigh Alarm 1 4 High Alarm 1 4 Low Alarm 1 4 Low or LowLow Alarm 1 4 LowLow Factory setting None Additional information Read access Operator Write acce...

Страница 161: ...ommunication V1 X1 4 V1 input selector Value percent selector Description Selects which value shall be transmitted as a 0 100 value in the V1 Z0 Z1 message Selection None Tank level Tank ullage AIO B1...

Страница 162: ...entry 0 to 63 Factory setting 15 Additional information Read access Operator Write access Maintenance No of preambles Navigation Setup Advanced setup Communication HART output Configuration No of pre...

Страница 163: ...Assigns a tank variable to the primary HART variable PV Selection None Tank level Tank ullage Measured level Distance Displacer position Water level Upper interface level Lower interface level Bottom...

Страница 164: ...variable PV User entry Signed floating point number Factory setting 0 mm Additional information Read access Operator Write access Maintenance 100 value Navigation Setup Advanced setup Communication H...

Страница 165: ...e of the primary HART variable PV Additional information Read access Operator Write access Percent of range Navigation Setup Advanced setup Communication HART output Configuration Percent of range Des...

Страница 166: ...3 value GP 4 value Factory setting Liquid temperature Additional information Read access Operator Write access Maintenance The Measured level option doesn t contain a unit If a unit is needed select t...

Страница 167: ...erature Vapor temperature Air temperature Observed density value Average profile density Upper density Middle density Lower density P1 bottom P2 middle P3 top GP 1 value GP 2 value GP 3 value GP 4 val...

Страница 168: ...nce Displacer position Water level Upper interface level Lower interface level Bottom level Tank reference height Liquid temperature Vapor temperature Air temperature Observed density value Average pr...

Страница 169: ...ernary variable QV Navigation Setup Advanced setup Communication HART output Configuration Quaternary variable QV Prerequisite Assign QV 168 None Description Shows the value of the fourth HART variabl...

Страница 170: ...8x Additional information Read access Operator Write access Maintenance Device tag Navigation Setup Advanced setup Communication HART output Information Device tag Description Enter a unique name for...

Страница 171: ...age 32 characters Factory setting NRF8x Additional information Read access Operator Write access Maintenance HART date code Navigation Setup Advanced setup Communication HART output Information HART d...

Страница 172: ...scription Defines the source of the level value Selection No input value HART device 1 15 level Level SR Level Displacer position AIO B1 3 value AIO C1 3 value AIP B4 8 value AIP C4 8 value Factory se...

Страница 173: ...0000 mm Factory setting Dependent on the device version Additional information Read access Operator Write access Maintenance Tank level Navigation Setup Advanced setup Application Tank configuration L...

Страница 174: ...Tank configuration Level Manual water level Prerequisite Water level source 173 Manual value Description Defines the manual value of the bottom water level User entry 2000 to 5000 mm Factory setting 0...

Страница 175: ...Selection Manual value HART device 1 15 temperature AIO B1 3 value AIO C1 3 value AIP B4 8 value AIP C4 8 value Factory setting Manual value Additional information Read access Operator Write access Ma...

Страница 176: ...cription Defines source from which the air temperature is obtained Selection Manual value HART device 1 15 temperature AIO B1 3 value AIO C1 3 value AIP B4 8 value AIP C4 8 value Factory setting Manua...

Страница 177: ...from which the vapor temperature is obtained Selection Manual value HART device 1 15 vapor temp AIO B1 3 value AIO C1 3 value AIP B4 8 value AIP C4 8 value Factory setting Manual value Additional info...

Страница 178: ...178 Endress Hauser Vapor temperature Navigation Setup Advanced setup Application Tank configuration Temperature Vapor temperature Description Shows the measured vapor temperature Additional informati...

Страница 179: ...ower density Factory setting Dependent on the device version Additional information Read access Operator Write access Maintenance Observed density Navigation Setup Advanced setup Application Tank conf...

Страница 180: ...Operator Write access Maintenance Vapor density Navigation Setup Advanced setup Application Tank configuration Density Vapor density Description Defines the density of the gas phase in the tank User e...

Страница 181: ...e AIP B4 8 value AIP C4 8 value Factory setting Manual value Additional information Read access Operator Write access Maintenance P1 bottom Navigation Setup Advanced setup Application Tank configurati...

Страница 182: ...ional information Read access Operator Write access Maintenance P1 offset Navigation Setup Advanced setup Application Tank configuration Pressure P1 offset Description Offset for the bottom pressure P...

Страница 183: ...P B4 8 value AIP C4 8 value Factory setting Manual value Additional information Read access Operator Write access Maintenance P2 middle Navigation Setup Advanced setup Application Tank configuration P...

Страница 184: ...bar Additional information Read access Operator Write access Maintenance P1 2 distance Navigation Setup Advanced setup Application Tank configuration Pressure P1 2 distance Description Defines the dis...

Страница 185: ...value AIP C4 8 value Factory setting Manual value Additional information Read access Operator Write access Maintenance P3 top Navigation Setup Advanced setup Application Tank configuration Pressure P...

Страница 186: ...ccess Operator Write access Maintenance P3 offset Navigation Setup Advanced setup Application Tank configuration Pressure P3 offset Description Offset for the top pressure P3 The offset is added to th...

Страница 187: ...te access Maintenance Ambient pressure Navigation Setup Advanced setup Application Tank configuration Pressure Ambient pressure Description Defines the manual value of the ambient pressure User entry...

Страница 188: ...e exerted by the liquid stored in the tank The compensation is based on a linear approximation obtained from manual hand dips at several levels distributed over the full range of the tank A B C D A002...

Страница 189: ...compared to the measured level a simple straight line method can be used with good results H 2 1 L L0 3 A0028724 51 Calculation of the HyTD correction 1 Linear correction according to Deformation fac...

Страница 190: ...e Navigation Setup Advanced setup Application Tank calculation HyTD HyTD mode Description Activates or deactivates the calculation of the Hydrostatic Tank Deformation Selection No Yes Factory setting...

Страница 191: ...Setup Advanced setup Application Tank calculation HyTD Deformation factor Description Defines the deformation factor for the HyTD change of device position per change of level User entry 1 0 to 1 0 Fa...

Страница 192: ...temperatures are based on manual or measured values and the temperature of the shell when the tank was calibrated for details refer to API MPMS Chapter 12 1 This correction is recommended for the fol...

Страница 193: ...ature atmosphere surrounding the tank CTSh Calculation of the wall temperature Depending on the parameters Covered tank 196 and Stilling well 197 the temperatures TW of the wetted and TD of the dry pa...

Страница 194: ...0030381 1 Covered tank 196 Covered Stilling well 197 Yes 2 Covered tank 196 Covered Stilling well 197 No 3 Covered tank 196 Open top Stilling well 197 Yes 4 Covered tank 196 Open top Stilling well 197...

Страница 195: ...028716 H Gauge Reference Height L Measured level TD Temperature of the dry part of the tank shell calculated from TP TV and TA TW Temperature of the wetted part of the tank shell calculated from TP TV...

Страница 196: ...value Additional information Read access Operator Write access CTSh mode Navigation Setup Advanced setup Application Tank calculation CTSh CTSh mode Description Activates or deactivates the CTSh Sele...

Страница 197: ...itional information Read access Operator Write access Maintenance Calibration temperature Navigation Setup Advanced setup Application Tank calculation CTSh Calibration temperature Description Specify...

Страница 198: ...Operating menu Tankside Monitor NRF81 198 Endress Hauser Additional information Read access Operator Write access Maintenance...

Страница 199: ...or both can be calculated HTG modes Four HTG modes can be selected in the HTG mode parameter 206 They determine which variables are measured and which are calculated Depending on the selected mode a...

Страница 200: ...distance P3 Top pressure Setup Advanced setup Tank configuration Pressure P3 top HP3 Position of P3 transmitter Setup Advanced setup Tank configuration Pressure P3 position P Density of the product 1...

Страница 201: ...d instead of the calculated value Safety distance This parameter defines the minimum amount of product which must be present above the pressure sensor P1 or P2 for the level or density calculation to...

Страница 202: ...2 3 4 D A0028719 1 P1 position 182 2 Safety distance 208 3 P1 2 distance 184 4 Safety distance 208 5 Minimum level 207 Level L is in area Calculation method for P Calculation method for L A calculated...

Страница 203: ...1 2 A B 3 P1 P2 P3 4 5 A0028717 1 P1 position 182 2 Safety distance 208 3 P1 2 distance 184 4 Safety distance 208 5 Minimum level 207 Level L is in area Calculation method for P Calculation method fo...

Страница 204: ...his problem a minimum pressure Pmin is defined in the Minimum pressure parameter 207 If the pressure measured by the sensor P1 or P2 respectively the software stops calculating the density and either...

Страница 205: ...rbances If the level oscillates around the changeover level Minimum level the algorithm will constantly switch between calculating the value and holding the previous result To avoid this effect a posi...

Страница 206: ...Operator Write access Tank level Navigation Setup Advanced setup Application Tank calculation HTG Tank level Description Shows the level calculated by HTG User interface Signed floating point number F...

Страница 207: ...etup Application Tank calculation HTG Minimum level Description Defines the minimum level below which no HTG calculation will take place User entry 0 to 20000 mm Factory setting 7000 mm Additional inf...

Страница 208: ...is used for the calculation User entry 0 to 10000 mm Factory setting 2000 mm Additional information Read access Operator Write access Maintenance Hysteresis Navigation Setup Advanced setup Application...

Страница 209: ...ssure Setup Advanced setup Tank configuration Pressure P1 bottom HP1 Position of P1 transmitter Setup Advanced setup Tank configuration Pressure P1 position P3 Top pressure Setup Advanced setup Tank c...

Страница 210: ...s a minimum thickness P P min A0028864 This is equivalent to the following condition for the product level L V H L P P P D min min 1 A0028863 Lmin is defined in the Minimum level parameter 212 As can...

Страница 211: ...de Description Defines the HTMS mode Depending on the mode one or two pressure transmitters are used Selection HTMS P1 HTMS P1 P3 Factory setting HTMS P1 Additional information Read access Operator Wr...

Страница 212: ...evel Description Defines the minimum product level for a HTMS calculation If Lp V falls below the limit defined in this parameter the density retains its last value or the manual value is used instead...

Страница 213: ...m Additional information Read access Operator Write access Maintenance Hysteresis Navigation Setup Advanced setup Application Tank calculation HTMS Hysteresis Description Defines the hysteresis for th...

Страница 214: ...Operating menu Tankside Monitor NRF81 214 Endress Hauser Additional information Read access Operator Write access Maintenance...

Страница 215: ...fines the alarm mode of the selected alarm Selection Off On Latching Factory setting Off Additional information Read access Operator Write access Maintenance Meaning of the options Off No alarms are g...

Страница 216: ...e 219 5 HH alarm 219 6 H alarm 220 7 L alarm 220 8 LL alarm 220 9 Clear alarm 221 Yes or power off on 10 Hysteresis 222 Error value Navigation Setup Advanced setup Application Alarm Alarm Error value...

Страница 217: ...Vapor density Middle density Upper density Correction Tank level GP 1 4 value Measured level P3 position Tank reference height Local gravity P1 position Manual density Tank ullage Average profile dens...

Страница 218: ...alue Navigation Setup Advanced setup Application Alarm Alarm HH alarm value Prerequisite Alarm mode 215 Off Description Defines the high high HH limit value User entry Signed floating point number Fac...

Страница 219: ...s Maintenance LL alarm value Navigation Setup Advanced setup Application Alarm Alarm LL alarm value Prerequisite Alarm mode 215 Off Description Defines the low low LL limit value User entry Signed flo...

Страница 220: ...H H alarm Prerequisite Alarm mode 215 Off Description Shows whether an HH or H alarm is currently active Additional information Read access Operator Write access L alarm Navigation Setup Advanced setu...

Страница 221: ...Any error Navigation Setup Advanced setup Application Alarm Alarm Any error Prerequisite Alarm mode 215 Off Description Show whether any alarm is currently active User interface Unknown Inactive Acti...

Страница 222: ...values The hystersis prevents constant changes of the alarm state if the level is near one of the limit values User entry Signed floating point number Factory setting 0 001 Additional information Rea...

Страница 223: ...ection English Deutsch Fran ais Espa ol Italiano Nederlands Portuguesa Polski Russian Svenska T rk e Chinese Japanese Korean Arabic Bahasa Indonesia Thai ti ng Vi t Vietnamese e tina Czech Factory set...

Страница 224: ...xt change is configured in the Display interval parameter 227 Value 1 to 4 display Navigation Setup Advanced setup Display Value 1 display Prerequisite The device has a local display Description Selec...

Страница 225: ...al places 1 Prerequisite The device has a local display Description This selection does not affect the measurement and calculation accuracy of the device Selection x x x x xx x xxx x xxxx Factory sett...

Страница 226: ...alid for distance values Header Navigation Setup Advanced setup Display Header Prerequisite The device has a local display Description Select header contents on local display Selection Device tag Free...

Страница 227: ...ry 1 to 10 s Factory setting 5 s Additional information Read access Operator Write access Operator Display damping Navigation Setup Advanced setup Display Display damping Prerequisite The device has a...

Страница 228: ...Write access Operator Contrast display Navigation Setup Advanced setup Display Contrast display Prerequisite The device has a local display Description Adjust local display contrast setting to ambien...

Страница 229: ...ormation Read access Operator Write access Maintenance If the Customer value option is selected the units are defined in the following parameters Distance unit 229 Pressure unit 230 Temperature unit 2...

Страница 230: ...ite access Maintenance if Units preset 121 Customer value Temperature unit Navigation Setup Advanced setup System units Temperature unit Description Select temperature unit Selection SI units C K US u...

Страница 231: ...Tankside Monitor NRF81 Operating menu Endress Hauser 231 Factory setting kg m Additional information Read access Operator Write access Maintenance if Units preset 121 Customer value...

Страница 232: ...ate time Set date Description Controls the setting of the real time clock Selection Please select Abort Start Confirm time Factory setting Please select Additional information Read access Operator Wri...

Страница 233: ...te Set date 232 Start Description Enter the current month User entry 1 to 12 Factory setting 1 Additional information Read access Operator Write access Maintenance Day Navigation Setup Advanced setup...

Страница 234: ...tory setting 0 Additional information Read access Operator Write access Maintenance Minute Navigation Setup Advanced setup Date time Minute Prerequisite Set date 232 Start Description Enter the curren...

Страница 235: ...ich describes the locking procedure and the parameters of this wizard Navigation Setup Advanced setup SIL confirmation Deactivate SIL WHG wizard The Deactivate SIL WHG wizard is only available for dev...

Страница 236: ...onfiguration data of the device can then always be modified The user is logged on in the Maintenance role The write protection affects all parameters marked with the symbol in this document Once the a...

Страница 237: ...several messages are active at the same time the messages with the highest priority is displayed Information on what is causing the message and remedy measures can be viewed via the symbol on the dis...

Страница 238: ...display Timestamp Navigation Diagnostics Timestamp Description Shows the timestamp of the previous diagnostic message Additional information Read access Operator Write access Operating time from resta...

Страница 239: ...e Monitor NRF81 Operating menu Endress Hauser 239 Date time Navigation Diagnostics Date time Description Displays the device internal real time clock Additional information Read access Operator Write...

Страница 240: ...c list Diagnostics 1 to 5 Description Display the current diagnostics messages with the highest to fifth highest priority Additional information The display consists of Symbol for event behavior Code...

Страница 241: ...Serial number Navigation Diagnostics Device information Serial number Description Shows the serial number of the measuring device Additional information Read access Operator Write access Firmware vers...

Страница 242: ...r Write access Device name Navigation Diagnostics Device information Device name Description Shows the name of the transmitter Additional information Read access Operator Write access Order code Navig...

Страница 243: ...Tankside Monitor NRF81 Operating menu Endress Hauser 243 The extended order code indicates the selected option of all ordering features and thus uniquely identifies the device...

Страница 244: ...e Diagnostic event simulation Navigation Diagnostics Simulation Diagnostic event simulation Description Select a diagnostic event to simulate this event Selection The diagnostic events of the device F...

Страница 245: ...rator Write access Maintenance Simulation value Navigation Diagnostics Simulation Simulation value Diagnostics Simulation Simulation value Prerequisite Current output simulation 244 On Description Def...

Страница 246: ...rameter 157 Communication status Parameter 127 Configuration Submenu 154 157 162 Contact type Parameter 150 Contrast display Parameter 228 Covered tank Parameter 196 CTSh Submenu 196 CTSh correction v...

Страница 247: ...ameter 206 HTMS Submenu 211 HTMS mode Parameter 211 Hysteresis Parameter 208 213 HyTD Submenu 190 HyTD correction value Parameter 190 HyTD mode Parameter 190 I Information Submenu 170 Input value Para...

Страница 248: ...165 Polling address Parameter 126 Pressure Submenu 118 181 Pressure unit Parameter 230 Previous diagnostics Parameter 237 Primary variable PV Parameter 165 Probe position Parameter 136 Process value...

Страница 249: ...TV Parameter 167 Timestamp Parameter 237 238 240 Trouble shooting 84 U Units preset Parameter 121 229 Upper interface level Parameter 113 Used for SIL WHG Parameter 146 152 V V1 address Parameter 157...