Commissioning
Micropilot S FMR533 4 to 20 mA HART
24
Hauser
5.4
Basic Setup with the device display
5.4.1
Function "measured value" (000)
This function displays the current measured value in the selected unit (see
"customer unit"
(042)
function). The number of digits after decimal point can be selected in the
"no.of
decimals" (095)
function. The length of the bargraph corresponds to the percental value of the
present measured value with regard to the span.
5.4.2
Function group "basic setup" (00)
5.4.3
Function "tank shape" (002)
This function is used to select the tank shape.
Selection:
• dome ceiling
• horizontal cyl
• bypass (Not weights and measures approved, accuracy is not guaranteed.
Recommendation: FMR532)
• stilling well (Not weights and measures approved, accuracy is not guaranteed.
Recommendation: FMR532)
•
flat ceiling
(Typical ceiling of storage tanks: a slight slope of only a few degrees can be neglected.)
• sphere
⇒
⇒
⇒