Commissioning
Micropilot S FMR533 4 to 20 mA HART
30
Hauser
5.4.11 Function "range of mapping" (052)
This function displays the suggested range of mapping. The reference point is always the
reference point of the measurement (
21). This value can be edited by the operator. For
manual mapping, the default value is: 0 m.
5.4.12 Function "start mapping" (053)
This function is used to start the interference echo mapping up to the distance given in
"range
of mapping" (052)
.
Selection:
•
off
: no mapping is carried out
• on: mapping is started
During the mapping process the message
"record mapping"
is displayed.
"
Caution!
A mapping will be recorded only, if the device is not in alarm-state.
5.4.13 Display "dist./meas.value" (008)
The
distance
measured from the reference point to the product surface and the
level
calculated
with the aid of the empty alignment are displayed again. Check whether the values correspond
to the actual level or the actual distance. The following cases can occur:
• Distance correct - level correct
È
continue with the next function
"check distance" (051)
• Distance correct - level incorrect
È
Check
"empty calibr" (005)
• Distance incorrect - level incorrect
È
continue with the next function
"check distance" (051)
⇒
⇒