2.3.7
Turn housing
After mounting, the housing can be turned 350° in order to simplify access to the display and
the terminal compartment. Proceed as follows to turn the housing to the required position:
• Undo the fixing screws (1)
• Turn the housing (2) in the required direction
• Tighten up the fixing screws (1)
L00-FMR533xx-17-00-00-de-008
2.4
Post-installation check
After the measuring device has been installed, perform the following checks:
• Is the measuring device damaged (visual check)?
• Does the measuring device correspond to the measuring point specifications such as process
temperature/pressure, ambient temperature, measuring range, etc.?
• Is the flange marking correctly aligned? (
• Have the flange screws been tightened up with the respective tightening torque?
• Are the measuring point number and labeling correct (visual check)?
• Is the measuring device adequately protected against rain and direct sunlight (see Chapter
"Accessories" in the Operating Instruction on CD-ROM)?
1
2
Allen key
4 mm (0.16 in)
tighten strongly
by hand