Micropilot S FMR533 4 to 20 mA HART
Commissioning
Hauser
29
L00-FMR2xxxx-14-00-06-en-010
distance = ok
• mapping is carried out up to the currently measured echo
• The range to be suppressed is suggested in the
"range of mapping" (052)
function
!
Note!
Anyway, it is wise to carry out a mapping even in this case.
dist. too small
• At the moment, an interference is being evaluated
• Therefore, a mapping is carried out including the presently measured echoes
• The range to be suppressed is suggested in the
"range of mapping" (052)
function
dist. too big
• This error cannot be remedied by interference echo mapping
• Check the application parameters
(002)
,
(003)
,
(004)
and
"empty calibr."
(005)
dist. unknown
If the actual distance is not known, no mapping can be carried out.
manual
A mapping is also possible by manual entry of the range to be suppressed. This entry is made in
the
"range of mapping" (052)
function.
"
Caution!
The range of mapping must end 0,5 m (1.6 ft) before the echo of the actual level. For an empty
tank, do not enter E, but E - 0,5 m (1.6 ft). If a mapping already exists, it is overwriten up to the
distance specified in
"range of mapping" (052)
. Beyond this value the existing mapping
remains unchanged.