Technical data
EngyVolt RV15
32
Reactive energy (kvarh)
±1 % of measuring range
THD
1 % up to 31st harmonic
Display repetition rate
1 s typically up to >99 % of the full scale value
Measurement and calculation interval
Max. 300 ms (maximum with %THD measurement)
Influence of ambient
temperature
Current and voltage: 0.013 %/°C (0.0072 %/°F) of nominal value
Power: 0.018 %/°C (0.01 %/°F) of measuring range
Error change due to variation
of an influence quantity in the
manner described in Section 6
of IEC 688:1992
2 x error allowed for the reference condition applied in the test. Error due to temperature variation
as above.
Error in measurement when a
measurand is within its
measuring range, but outside
its reference range
2 x error allowed at the end of the reference range adjacent to the section of the measuring range,
where the measurand is currently operating / being tested.
Warm-up period
1 minute
10.5
Installation
Mounting location
EngyVolt RV15
Panel cutout as per DIN 96, max. thickness 5 mm (0.2 in)
The device is secured using the snap-on fastening unit which is integrated in the housing. When
mounting, make sure there is sufficient room to connect cables and wires on all sides of the measuring
device.
Orientation
Vertical
10.6
Environment
Ambient temperature range
–10 to 55 °C (14 to 131 °F)
Storage temperature
–20 to 70 °C (–4 to 158 °F)
Humidity
0 to 90 %, non-condensing
Altitude
Up to 2
000 m (6
560 ft)