Commissioning
EngyVolt RV15
26
5. Press the key to confirm your selection.
"SET" is displayed. The device returns to the first menu level.
6.3.9
Self-test – TEST
This screen contains several functions for performing self-tests on the multifunction electrical energy
meter.
1. Call up the Setup menu.
2. Press the or keys until TEST is displayed.
3. Press the key.
4. Use the and keys to choose from the following values: diSP ON (when selected by pressing
the key, all the segments of the LCD display are switched on to allow users to detect a
segment failure); diSP TOGL (when selected by pressing the key, the display alternates
between two different display modes. This helps the user identify whether individual segments
do not switch off); PHAS SEQ (when selected by pressing the key, this function checks
whether the voltage and current connections have been established correctly on the energy
meter. PSEQ (phase sequence), V 123, I 123 is displayed if all the connections are correct. If
PSEQ, V 132, I 123, for example, is displayed, this indicates that a voltage connection is faulty.
If PSEQ, V 12_, I 123, for example, is displayed, this indicates that a voltage connection is
missing.
6.3.10 Displaying the software version – SOFT
This function directly displays the version of the internal software (firmware).
1. Call up the Setup menu.
2. Press the or keys until SOFT is displayed.
3. Press the key.
Содержание EngyVolt RV15