Appendix
EngyVolt RV15
42
Address
(Register)
Parameter
number
Parameter
Holding register
Modbus start address
Hex
Valid range
Mode
High Byte
Low Byte
40025
13
Password
00
18
Write password for access to protected
registers. Read zero.
Default: 0000
Reading will also reset the password
timeout back to one minute.
r/w
40029
15
Network baud rate
00
1C
Write the network port baud rate for
Modbus protocol.
Valid values:
0 = 2400 baud
1 = 4800 baud
2 = 9600 baud (default)
3 = 19200 baud
4 = 38400 baud
Requires a restart to become effective.
r/w
40031
16
Energy units prefix
00
1E
Write the units prefix for energy output
values.
0 = k (e.g. kWh, but Ah for ampere
hours - default)
1 = M (e.g. MWh, but kAh for ampere
hours)
r/w
40037
19
System power
00
24
Read the total system power,
e.g. for 3p4w returns System Volts x
System Amps x 3.
ro
40041
21
Register order
00
28
Write the value 2141 in the required
register order.
r/w
40043
22
Serial number Hi
00
2A
Read the first product serial number.
ro
40045
23
Serial Number Lo
00
2C
Read the second product serial number.
ro
40087
44
Relay 1 energy type
00
56
Write MODBUS Protocol input
parameter for pulse relay 1
0 = relay off
37 = import Wh
39 = import varh
Default = 37
r/w
40089
45
Relay 2 energy type
00
58
Write MODBUS Protocol input
parameter for pulse relay 1
0 = relay off
37 = import Wh
39 = import varh
Default = 37
r/w
40217
109
Reset logged data
00
D8
Write code to reset data group.
1 = energy
2 = demand maximums
3 = demand maximums and demand
time
r/w
Register order
Register order controls the order in which the device receives or sends floating-point numbers: -
normal or reversed register order. In normal mode, the two registers that make up a floating point
number are sent most significant register first. In reversed register mode, the two registers that make
up a floating point number are sent least significant register first. To set the mode, write the value
'2141.0' into this register - the instrument will detect the order used to send this value and set that
order for all Modbus Protocol transactions involving floating point numbers.
It is perfectly feasible to change EngyVolt devices set-up using a general purpose Modbus Protocol
master, but often easier to use the device display, especially for gaining password protected access.