EngyVolt RV15
Appendix
41
11.2.3 Modbus protocol holding registers and EngyVolt set up
Holding registers are used to store and display instrument configuration settings. All holding registers
not listed in the table below should be considered as reserved for manufacturer use and no attempt
should be made to modify their values. The holding register parameters may be viewed or changed
using the Modbus Protocol. Each parameter is held in two consecutive 4X registers. Modbus Protocol
Function Code 03 is used to read the parameter and Function Code 16 is used to write. Write to
only one parameter per message.
Address
(Register)
Parameter
number
Parameter
Holding register
Modbus start address
Hex
Valid range
Mode
High Byte
Low Byte
40001
1
Demand time (
D
t)
00
00
Read minutes into first demand
calculation. When the Demand Time
reaches the Demand Period then the
demand values are valid.
ro
40003
2
Demand period (
D
t)
00
02
Write demand period: 0, 5, 8, 10, 15,
20, 30 or 60 minutes.
Default: 60 minutes.
Setting the period to 0 will cause the
demand to show the current parameter
value, and demand max to show the
maximum parameter value since last
demand reset.
r/w
40007
4
System Volts
00
06
Read system voltage, VLL for 3P3W,
VLN for others.
ro
40009
5
System current
00
08
Write system current, limited to
1 to 9
999 A. Requires password, see
parameter 13
r/w
40011
6
System type
00
0A
Write system type
3p4w = 3
3p3w = 2
1p2w = 1
Requires password, see parameter 13
r/w
40013
7
Relay pulse width
00
0C
Write relay on period in milliseconds:
60, 100, 200
Default: 200
r/w
40015
8
Password lock
00
0E
Write any value to password lock
protected registers.
Read password lock status:
0 = locked
1 = unlocked
Reading will also reset the password
timeout back to one minute.
r/w
40019
10
Network parity stop
00
12
Write the network port parity/stop bits
for Modbus Protocol, where
0 = One stop bit and no parity, default.
1 = One stop bit and even parity.
2 = One stop bit and odd parity.
3 = Two stop bits and no parity.
Requires a restart to become effective.
r/w
40021
11
Network node
00
14
Write the network port node address: 1
to 247 for Modbus protocol.
Default: 1
Valid range 1 to 247.
Requires a restart to become effective.
Note, both the Modbus protocol and
Johnson Controls node addresses can be
changed via the display setup menus.
r/w
40023
12
Pulse divisor
00
16
Write pulse divisor index:
N = 2 to 6 in Wh/10
N
.
Default: 3
r/w