Appendix
EngyVolt RV15
40
Address
(Register)
Parameter
number
EngyVolt input register parameter description
Modbus-Startadresse Hex
3 Ø 3 Ø 1 Ø
Unit
Hi Byte
Lo Byte
4
W
3
W
2
W
30085
43
Total system power demand
D
t (*4)
Watt
00
54
Â
Â
Â
30087
44
Maximum total system power demand
D
t (*4)
Watt
00
56
Â
Â
Â
30101
51
Total system VA demand
D
t
VA
00
64
Â
Â
Â
30103
52
Maximum total system VA demand
D
t
VA
00
66
Â
Â
Â
30105
53
Neutral current demand
D
t
Ampere
00
68
Â
Ä
Ä
30107
54
Maximum neutral current demand
D
t
Ampere
00
6A
Â
Ä
Ä
30201
101
Line 1 to Line 2 volts
Volt
00
C8
Â
Â
Ä
30203
102
Line 2 to Line 3 volts
Volt
00
CA
Â
Â
Ä
30205
103
Line 3 to Line 1 volts
Volt
00
CC
Â
Â
Ä
30207
104
Average line to line volts
Volt
00
CE
Â
Â
Ä
30225
113
Neutral current
Ampere
00
E0
Â
Ä
Ä
30235
118
Phase 1 L/N volts THD
%
00
EA
Â
Ä
Â
30237
119
Phase 2 L/N volts THD
%
00
EC
Â
Ä
Ä
30239
120
Phase 3 L/N volts THD
%
00
EE
Â
Ä
Ä
30241
121
Phase 1 Current THD
%
00
F0
Â
Â
Â
30243
122
Phase 2 Current THD
%
00
F2
Â
Â
Ä
30245
123
Phase 3 Current THD
%
00
F4
Â
Â
Ä
30249
125
Average line to neutral volts THD
%
00
F8
Â
Ä
Â
30251
126
Average line current THD
%
00
FA
Â
Â
Â
30255
128
-Total system power factor (*5)
Degrees
00
FE
Â
Â
Â
30259
130
Phase 1 current demand
D
t
Ampere
01
02
Â
Â
Â
30261
131
Phase 2 current demand
D
t
Ampere
01
04
Â
Â
Ä
30263
132
Phase 3 current demand
D
t
Ampere
01
06
Â
Â
Ä
30265
133
Maximum phase 1 current demand
D
t
Ampere
01
08
Â
Â
Â
30267
134
Maximum phase 2 current demand
D
t
Ampere
01
0A
Â
Â
Ä
30269
135
Maximum phase 3 current demand
D
t
Ampere
01
0C
Â
Â
Ä
30335
168
Line 1 to line 2 volts THD
%
01
4E
Â
Â
Ä
30337
169
Line 2 to line 3 volts THD
%
01
50
Â
Â
Ä
30339
170
Line 3 to line 1 volts THD
%
01
52
Â
Â
Ä
30341
171
Average line to line volts THD
%
01
54
Â
Â
Ä
*1)
The power factor has its sign adjusted to indicate the nature of the load. Positive for capacitive and negative
for inductive.
2*)
There is a user option to select either k or M for the energy prefix.
3*)
The same user option as in 2 above gives a prefix of none or k for Amphours
4*)
The power sum demand calculation is for import power only.
5*)
The negative total system power factor is a sign inverted version of parameter 32, the magnitude is the same
as parameter 32.
6*)
There is a user option to select None, k or M for the energy prefix.