Appendix
EngyVolt RV15
54
Field name
Example (Hex)
Number of points High 00
Number of points Low 02
Error check Low
C4
Error check High
0B
Data must be requested in register pairs i.e. the “Starting Address“ and the “Number of Points”
must be even numbers to request a floating point variable. If the “Starting Address” or the
“Number of points” is odd then the query will fall in the middle of a floating point variable the
product will return an error message.
The following response returns the contents of Demand Time as 1, But see also “Exception
Response” later.
Field name
Example (Hex)
Slave address
01
Function
03
Byte count
04
Data, High Reg, High Byte 3F
Data, High Reg, Low Byte 80
Data, Low Reg, High Byte 00
Data, Low Reg, Low Byte 00
Error check Low
F7
Error check High
CF
Write holding registers
MODBUS Protocol code 10 (16 decimal) writes the contents of the 4X registers.
The following query will set the Demand Period to 60, which effectively resets the Demand Time:
Field name
Example (Hex)
Slave address
01
Function
10
Starting address High
00
Starting address Low
00
Number of registers High
00
Number of registers Low
02
Byte count
04
Data, High Reg, High Byte 00
Data, High Reg, Low Byte 00
Data, Low Reg, High Byte 00
Data, Low Reg, Low Byte 00
Error check Low
F2
Error check High
AF