EngyVolt RV15
Appendix
39
Amps 2 (current Phase 2) Start address
= 0008
No of registers
= 0002
Each request for data must be restricted to 40 parameters or less. Exceeding the 40 parameter limit
will cause a Modbus Protocol exception code to be returned.
Address
(Register)
Parameter
number
EngyVolt input register parameter description
Modbus-Startadresse Hex
3 Ø 3 Ø 1 Ø
Unit
Hi Byte
Lo Byte
4
W
3
W
2
W
30001
1
Phase 1 line to neutral volts
Volt
00
00
Â
Ä
Â
30003
2
Phase 2 line to neutral volts
Volt
00
02
Â
Ä
Ä
30005
3
Phase 3 line to neutral volts
Volt
00
04
Â
Ä
Ä
30007
4
Phase 1 current
Ampere
00
06
Â
Â
Â
30009
5
Phase 2 current
Ampere
00
08
Â
Â
Ä
30011
6
Phase 3 current
Ampere
00
0A
Â
Â
Ä
30013
7
Phase 1 power
Watt
00
0C
Â
Ä
Â
30015
8
Phase 2 power
Watt
00
0E
Â
Ä
Ä
30017
9
Phase 3 power
Watt
00
10
Â
Ä
Ä
30019
10
Phase 1 volt amps
VA
00
12
Â
Ä
Â
30021
11
Phase 2 volt amps
VA
00
14
Â
Ä
Ä
30023
12
Phase 3 volt amps
VA
00
16
Â
Ä
Ä
30025
13
Phase 1 volt amps reactive
Var
00
18
Â
Ä
Â
30027
14
Phase 2 volt amps reactive
Var
00
1A
Â
Ä
Ä
30029
15
Phase 3 volt amps reactive
var
00
1C
Â
Ä
Ä
30031
16
Phase 1 power factor (*1).
-
00
1E
Â
Ä
Â
30033
17
Phase 2 power factor (*1)
-
00
20
Â
Ä
Ä
30035
18
Phase 3 power factor (*1)
-
00
22
Â
Ä
Ä
30037
19
Phase 1 phase angle
Degrees
00
24
Â
Ä
Â
30039
20
Phase 2 phase angle
Degrees
00
26
Â
Ä
Ä
30041
21
Phase 3 phase angle
Degrees
00
28
Â
Ä
Ä
30043
22
Average line to neutral volts
Volt
00
2A
Â
Ä
Ä
30047
24
Average line current
Ampere
00
2E
Â
Â
Â
30049
25
Sum of line currents
Ampere
00
30
Â
Â
Â
30053
27
Total system power.
Watt
00
34
Â
Â
Â
30057
29
Total system volt amps
VA
00
38
Â
Â
Â
30061
31
Total system Var.
var
00
3C
Â
Â
Â
30063
32
Total system power factor (*1)
-
00
3E
Â
Â
Â
30067
34
Total system phase angle
Degrees
00
42
Â
Â
Â
30071
36
Frequency of supply voltages
Hz
00
46
Â
Â
Â
30073
37
Import Wh since last reset (*2)
kWh/MWh
00
48
Â
Â
Â
30075
38
Export Wh since last reset (*2)
kWh/MWh
00
4A
Â
Â
Â
30077
39
Import varh since last reset (*2)
kvarh/Mvarh
00
4C
Â
Â
Â
30079
40
Export varh since last reset (*2)
kvarh/Mvarh
00
4E
Â
Â
Â
30081
41
VAh since last reset (*2)
kVAh/MVAh
00
50
Â
Â
Â
30083
42
Ah since last reset (*3)
Ah/kAh
00
52
Â
Â
Â
Содержание EngyVolt RV15