RS485 MODBUS
Number
EngyVolt RV12: 1
EngyVolt RV15: 1 (optional, via extension module)
Type
Two-wire, half-duplex
Baud rate
2400, 4800, 9600, 19200, 38400
10.3
Power supply
Supply voltage
AC nominal voltage
110 to 400 V AC ±10 %
DC nominal voltage
120 to 350 V DC ±20 %
Power consumption
5 VA
Electrical connection
The measuring device is designed exclusively for operation on external current
converters.
The multifunction EngyVolt RV12 and RV15 electrical energy meters are suitable for single-phase
and three-phase power systems with 3 or 4 wires.
The "S2" secondary terminals of the current converters are connected in the electrical energy meter.
Only one protective ground connection
*
is provided for this reason.
Terminals
Screw-clamp terminals 0.05 to 2.5 mm² (30 to 14 AWG)
10.4
Performance characteristics
Reference operating
conditions
Reference temperature
23 °C ±1 °C (73.4 °F ±1.8 °F)
Input wave form
50 or 60 Hz ±2 %
Sinusoidal (distortion factor < 0.005)
Supply voltage
Nominal voltage ±1 %
Supply voltage frequency (with AC) Nominal frequency ±1 %
Supply voltage wave form
Sinusoidal (distortion factor < 0.05)
Maximum measured error
Extended measured error: IEC 688: 1992
Current (A)
0.5 % of nominal current
Voltage (V)
0.5 % of max. nominal voltage (4 % for I2 in 3-phase 3-wire operation)
Calculated neutral current (A)
4 % of nominal current
Frequency (Hz)
0.1 Hz
Power factor (PF = Cos-Phi)
0 to 1
Power factor is only indicated when the measured VA is over 3 % of range maximum
Active power (W)
±1 % of nominal power
Reactive power (var)
±1 % of nominal power
Apparent power (VA)
±1 % of nominal power
Active energy (kWh)
Class 1 (IEC 62053-21)