99
Reference Manual
00809-0100-4021, Rev GC
Section 3: HART commissioning
April 2014
A HART-based communicator can test, configure, and format a multidropped 3144P
transmitter the same as in a standard point-to-point installation.
Note
The 3144P is set to address 0 at the factory, allowing it to operate in the standard point-to-point
manner with a 4–20 mA output signal. To activate multidrop communication, the transmitter
address must be changed to a number between 1 and 15, which deactivates the 4–20 mA
analog output, sending it to a fixed 4 mA output. The failure mode current is also disabled. It
also disables the failure mode alarm signal, which is controlled by the upscale/downscale
switch/jumper position. Failure signals in multidropped transmitters are communicated
through HART messages.
3.13
Use with the HART Tri-Loop
To prepare the 3144P transmitter with dual-sensor option for use with a Rosemount 333 HART
Tri-Loop, the transmitter must be configured to Burst Mode and the process variable output
order must be set. In Burst Mode, the transmitter provides digital information for the four
process variables to the HART Tri-Loop. The HART Tri-Loop divides the signal into separate 4–20
mA loops for up to three of the following choices:
primary variable (PV)
secondary variable (SV)
tertiary variable (TV)
quaternary variable (QV)
When using the 3144P transmitter with dual-sensor option in conjunction with the HART
Tri-Loop, consider the configuration of the differential, average, first good temperatures, Sensor
Drift Alert, and the Hot Backup feature (if applicable).
Note
The procedures are to be used when the sensors and transmitters are connected, powered, and
functioning properly. Also, a field communicator must be connected and communicating to the
transmitter control loop. For communicator usage instructions, see
.
Set the transmitter to Burst Mode
Set process variable output order
Note
Take careful note of the process variable output order. The HART Tri-Loop must be configured to
read the variables in the same order.
HART 5 Fast Keys
2, 2, 8, 4
HART 7 Fast Keys
2, 2, 8, 4
HART 5 Fast Keys
2, 2, 8, 5
HART 7 Fast Keys
2, 2, 8, 5
Содержание Rosemount
Страница 1: ...Reference Manual 00809 0100 4021 Rev GC April 2014 Rosemount 3144P Temperature Transmitter ...
Страница 2: ......
Страница 4: ...iv Reference Manual 00809 0100 4021 Rev GC Title Page April 2014 ...
Страница 10: ...x Reference Manual 00809 0100 4021 Rev GC Table of Contents April 2014 Table of Contents ...
Страница 38: ...28 Reference Manual 00809 0100 4021 Rev GC Section 2 Installation April 2014 Installation ...
Страница 188: ...178 Reference Manual 00809 0100 4021 Rev GC Section 5 Maintenance April 2014 Maintenance ...
Страница 233: ...227 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 234: ...228 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 235: ...229 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 237: ...231 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 238: ...232 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 244: ...238 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 250: ...Index 244 Reference Manual 00809 0100 4021 Rev GC Index April 2014 Index ...
Страница 251: ......