13
Reference Manual
00809-0100-4021, Rev GC
Section 2: Installation
April 2014
Write protect switch (HART and F
OUNDATION
fieldbus)
The transmitter is equipped with a write-protect switch that can be positioned to prevent
accidental or deliberate change of configuration data.
Alarm switch (HART)
An automatic diagnostic routine monitors the transmitter during normal operation. If the
diagnostic routine detects a sensor failure or an electronics failure, the transmitter goes into
alarm (high or low, depending on the position of the failure mode switch).
The analog alarm and saturation values used by the transmitter depend on whether it is
configured to standard or NAMUR-compliant operation. These values are also custom-configu-
rable in both the factory and the field using the HART Communications. The limits are:
21.0
I
23 for high alarm
3.5
I
3.75 for low alarm
Table 2-1. Values for standard and NAMUR operation
Simulate switch (F
OUNDATION
fieldbus)
Simulate switch is used to replace the channel value coming from the Sensor Transducer Block.
For testing purposes, it manually simulates the output of the Analog Input Block to a desired
value.
2.3
Mounting
If possible, the transmitter should be mounted at a high point in the conduit run so moisture
from the conduits will not drain into the housing. The terminal compartment could fill with
water if the transmitter is mounted at a low point in the conduit run. In some instances, the
installation of a poured conduit seal, such as the one pictured in
, is advisable. Remove
the terminal compartment cover periodically and inspect the transmitter for moisture and
corrosion.
Standard operation (factory default)
NAMUR-compliant operation
Fail High
21.75 mA
I
23.0 mA
Fail High
21 mA
I
23.0 mA
High Saturation
I
20.5 mA
High Saturation
I
20.5 mA
Low Saturation
I
3.90 mA
Low Saturation
I
3.8 mA
Fail Low
I
3.75 mA
Fail Low
I
3.6 mA
Содержание Rosemount
Страница 1: ...Reference Manual 00809 0100 4021 Rev GC April 2014 Rosemount 3144P Temperature Transmitter ...
Страница 2: ......
Страница 4: ...iv Reference Manual 00809 0100 4021 Rev GC Title Page April 2014 ...
Страница 10: ...x Reference Manual 00809 0100 4021 Rev GC Table of Contents April 2014 Table of Contents ...
Страница 38: ...28 Reference Manual 00809 0100 4021 Rev GC Section 2 Installation April 2014 Installation ...
Страница 188: ...178 Reference Manual 00809 0100 4021 Rev GC Section 5 Maintenance April 2014 Maintenance ...
Страница 233: ...227 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 234: ...228 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 235: ...229 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 237: ...231 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 238: ...232 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 244: ...238 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 250: ...Index 244 Reference Manual 00809 0100 4021 Rev GC Index April 2014 Index ...
Страница 251: ......