180
Reference Manual
00809-0100-4021, Rev GC
Section 6: Certified Safety Instrumented System (Safety-Certified)
April 2014
Certified safety instrumented system (safety-certified)
3.
Check the Namur Software Revision located on the adhesive transmitter tag.
“SW Rev _._._”.
If the Device label software revision is 1.1.1 or higher, the device is safety certified.
4.
You can also identify a certified 3144P by its Device Revision which can be found using
any HART compliant communicator.
For the 3144P, certified device revisions are as follows:
–
Device Revision 5.x (HART 5)
–
Device Revision 6.x (HART 7)
6.3
Installation
No special installation is required in addition to the standard installation practices outlined in
this document. Always ensure a proper seal by installing the electronics housing cover(s) so that
metal contacts metal.
The loop should be designed so the terminal voltage does not drop below 12 Vdc when the
transmitter output is 24.5 mA.
6.4
Commissioning
The 3144P Safety Certified Transmitter can be commissioned by a person with average
knowledge of Rosemount temperature transmitters and the configuration device being used.
Please refer to
“Confirm HART revision capability” on page 8
to confirm your system's HART
Revision capability and to confirm the installation of the correct device drivers (separate drivers
required for HART 5 and HART 7).
To commission the 3144P Safety Certified Transmitter using a 375/475 Field Communicator,
use the
.
6.5
Configuration
Use any HART capable configuration tool or the optional local operator interface to
communicate with and verify the initial configuration or any configuration changes made to the
3144P prior to operating in Safety Mode. All configuration methods outlined in
are the
same for the safety certified 3144P temperature transmitter with any differences noted.
6.6
Safety messages
Procedures and instructions in this section may require special precautions to ensure the safety
of the personnel performing the operations. Information that raises potential safety issues is
indicated by a warning symbol ( ). Refer to the following safety messages before performing
an operation preceded by this symbol.
Содержание Rosemount
Страница 1: ...Reference Manual 00809 0100 4021 Rev GC April 2014 Rosemount 3144P Temperature Transmitter ...
Страница 2: ......
Страница 4: ...iv Reference Manual 00809 0100 4021 Rev GC Title Page April 2014 ...
Страница 10: ...x Reference Manual 00809 0100 4021 Rev GC Table of Contents April 2014 Table of Contents ...
Страница 38: ...28 Reference Manual 00809 0100 4021 Rev GC Section 2 Installation April 2014 Installation ...
Страница 188: ...178 Reference Manual 00809 0100 4021 Rev GC Section 5 Maintenance April 2014 Maintenance ...
Страница 233: ...227 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 234: ...228 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 235: ...229 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 237: ...231 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 238: ...232 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 244: ...238 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 250: ...Index 244 Reference Manual 00809 0100 4021 Rev GC Index April 2014 Index ...
Страница 251: ......