Appendix A: Reference Data
April 2014
Temperature limits
Field communicator connections
Field communicator connections are permanently fixed to power/signal block.
Failure mode
The 3144P features software and hardware failure mode detection. An independent circuit
is designed to provide backup alarm output if the microprocessor hardware or software fails.
The alarm level is user-selectable using the failure mode switch. If failure occurs, the position of
the hardware switch determines the direction in which the output is driven (HIGH or LOW). The
switch feeds into the digital-to-analog (D/A) converter, which drives the proper alarm output
even if the microprocessor fails. The values at which the transmitter drives its output in failure
mode depends on whether it is configured to standard, or NAMUR-compliant (NAMUR
recommendation NE 43, 2003) operation. The values for standard and NAMUR-compliant
operation are as follows:
Load limitations
Note
HART Communication requires a loop resistance between 250 and 1100 ohms. Do not
communicate with the transmitter when power is below 12 Vdc at the transmitter terminals.
Description
Operating limit
Storage limit
Without LCD display
–40 to 185 °F
–40 to 85 °C
–60 to 250 °F
–50 to 120 °C
With LCD display Meter
–4 to 185 °F
–20 to 85 °C
–50 to 185 °F
–45 to 85 °C
Table A-2. Operation Parameters
Standard
(1)
(1) Measured in milliamperes
NAMUR-Compliant
Linear Output:
3.9
I
20.5
3.8
I
20.5
Fail HIGH:
21.75
I
23 (default)
21.5
I
23 (default)
Fail Low:
I
3.75
I
3.6
Maximum Load = 40.8 X (Supply Voltage - 12.0)
(1)
(1) Without transient protection (optional).
1240
1000
750
250
0
10
12.0 Min
18.1
30
42.4
Supply Voltage (Vdc)
HART and Analog
Operating Range
4–20 mA dc
Lo
ad
(
O
h
m
s)
500
1100
Analog Only
Operating Range
Содержание Rosemount
Страница 1: ...Reference Manual 00809 0100 4021 Rev GC April 2014 Rosemount 3144P Temperature Transmitter ...
Страница 2: ......
Страница 4: ...iv Reference Manual 00809 0100 4021 Rev GC Title Page April 2014 ...
Страница 10: ...x Reference Manual 00809 0100 4021 Rev GC Table of Contents April 2014 Table of Contents ...
Страница 38: ...28 Reference Manual 00809 0100 4021 Rev GC Section 2 Installation April 2014 Installation ...
Страница 188: ...178 Reference Manual 00809 0100 4021 Rev GC Section 5 Maintenance April 2014 Maintenance ...
Страница 233: ...227 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 234: ...228 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 235: ...229 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 237: ...231 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 238: ...232 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 244: ...238 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 250: ...Index 244 Reference Manual 00809 0100 4021 Rev GC Index April 2014 Index ...
Страница 251: ......